Oil Heating Airflow Test

    - with Darrell Udelhoven - HVAC RETIRED - udarrell  My Scan of My Oil Furnace Blower Curve   While the image loads switch back & read this page
Below is an example of this problem with a (Thermo Pride OL 11 oil furnace).
The low airflow probable cause is "an unbalanced airflow heatload through the evaporator coil, along with an airflow restriction due to the evaporator coil being too close to the large oil furnace heat exchanger.  

When installing evaporator coils on an oil furnace, due to the extra-large heat exchanger that is near the top of the furnace, the coil should be set well above the heat exchanger using sheet metal to channel the air into the air intake of the evaporator coil. This will optimize the directional velocity which will increasing the flow and throw through the supply diffusers.

When the evaporator is set directly on top of the furnace it results in a restriction of airflow along with extreme backpressure turbulence, which results in a loss of both velocity and static pressure in the main supply trunk. The mfg'ers need to re-engineer the distance from the heat exchangers and design effective transitions to the intake area of the evaporator coils.

Additionally, the return air intake should be at the ceiling level, in order to properly heat load the evaporator coil. Old gravity flow supply registers should be converted to diffusers, in order to achieve the proper air throw across the room.

To achieve maximum airflow efficiency, --the supply air and return air ductwork must be properly sized, along with oversizing the filter grille areas.
===============

This is merely an illustration of some useful oil heating airflow testing procedures.  This airflow test is easy to do using a thermometer, --so bear with me.  The results only provide an estimate of cfm airflow, the real clincher for summer airconditioning, is whether, the system is merely "recycling the cold air" due to the return air and supply air being at the floor level.

The chemical energy of furnace fuel oil is nominally rated at 140,000-Btu-per-gal (140,000 Btu/gal)
Fuel oil pressure to the nozzle, on residential oil heat is
nominally rated at a setting of 100-psi.

My oil furnace is rated at 140,000-btuh input with a one/gal per/hr nozzle and 119,000 input with a (0.85) gal/hr nozzle.

At the nominal 100-psi oil pressure to the nozzle my furnace has a .85-gal/hr nozzle yielding 119,000-btu/hr input, at 78% efficiency, it should yield around 92,820-btu/hr output.

Use the room return air temperature subtracted from the supply air plenum temperature or the closest Supply Air register temperature.  You can read the temperature from a lot of the fan center switches located on the furnace or up on the plenum.

Formula is: CFM= Btuh output of 92,820-btuh / divided by (i.e., Temp rise 90ºF  times  1.08 or 97.2ºF) = 954-CFM
========
The blower curve graph on my ThermoPride OL 11 illustrates the devastation of doubling the static pressure. Coupled with the return air and supply air being at the floor level, and supply air registers that do not through the cold air upward, the cold air recycling will cause an under heat loaded evaporator coil!

My model OL 11 Thermo Pride, has a quarter HP blower motor, as there is no central air conditioning. (It is a Belt Drive Blower.)


With return air registers and supply diffusers at floor level you have a recycling of cold air which makes it extra difficult to heat load the evaporator coil! An adequate "Temperature Difference" between return air and supply air is absolutely necessary for the evaporator coil to absorb the rated btuh heat load and transfer it to the outside condenser coils.

In northern colder climates, we need some innovative engineering to make it easy to switch from floor to near the ceiling Supply Air/Return Air operation in the summer. The system should also be engineered to provide adequate throw across rooms from the supply air diffusers!


Required fan motor HP varies as to the cube of the rpm blower speed.

My ThermoPride OL 11 Oil furnace has a quarter Hp motor "belt drive blower" producing around 982-cfm. At 700-rpm the graph shows around 0.33" SP at 982-cfm. I have pleaded filters over three (14" X 25") floor returns and another (20" X 25") in the furnace, for a total of 4 filters.

Keeping the total static pressure as low as possible and within mfg'ers ESP requirements for air conditioning is the first requirement in an efficient system design.

BTW, what is the average pressure drop across the new +90 high efficiency furnace condensers? That pressure drop should be published by all of the companies!
====================================

My Scan of My ThermoPride OL 11 Graphed Blower-Curve-Chart
Thermopride OL 11 Graph ipg image - Thank you Dave Staso, CA. for the better expandable image!
"After it loads Right click "Show Original Images" - Move cursor arrow over graph - Click + when 'over graph' for expanded image," then print on the highest quality setting.

Every manufacturer should furnish blower curve charts with their units and also put them on the Internet for service tech's to download and print. Also, air conditioning codes should be updated in respect to proper sizing of the duct work which must include all the pressure inducing factors when sizing the supply and return ducts. Also, illustrate best furnace to evaporator coil transitions, especially on oil furnaces!  You should always keep the ESP to 0.5" or mfg'ers listing.

The evaporator must be mounted 4 to 6 inches above this model oil furnace to achieve adequate airflow!

Also, air conditioning codes should be updated in respect to proper sizing of the ductwork, which must include all the pressure inducing factors when sizing the supply and return duct systems.

 
(Air Conditioning Systems) Typical Static Pressure difference before the fan to after the coil in existing installations averaged 0.54 inches of water column (134 Pa). Darrell U.

On an upflow furnace, External Static Pressure is measured before the E-Coil to determine your  the mfg'ers ESP Ratings.

Therefore, every manufacturer should furnish blower line curve charts with their units and put them on the Internet for service tech's to download and print. A true graph chart, worthy of printing and discerning the variables of belt drive blowers. Observe how easy it is to fall below the required CFM with a quarter horse blower belt drive motor that was standard with 112,000 btuh output oil furnaces. Measuring the static pressure of the duct system is a must!

The design of the oil furnace with its ultra large heat exchanger coming to near the top of the furnace and the blower set to the side of the furnace is an engineered airflow problem. The blower set to the side blows against the heat exchanger and the back of the furnace which blocks directional airflow velocity thus generating high initial velocity & static back pressures against the blower.

Most installers set the A-Coil directly on top of the furnace with no transitions resulting in another restriction and more blocking of directional velocity airflow and a huge leap in (ESP) static pressures'. Thermo pride states that the A-Coil must be at least 3" above the furnace. That might work for a small 1.5 or 2-ton A/C, but what about a 3 to 5-ton A/C's required airflow?

In my opinion, these low boy oil furnaces should be designed with space above the heat exchanger depending on the airflow requirements of the air conditioning application size to be used. There should also be a transition beginning at the top of the heat exchanger and transitioning to the intake area of the evaporator coil. This would greatly reduce the backpressure and improve airflow. The worst place to lose velocity and generate static back-pressure is below the evaporator coil. Where it needs the velocity and static pressures' is at the diffusers.

The low airflow probable cause is "an unbalanced airflow heatload through the evaporator coil, along with "back pressure and extreme turbulence," due to the evaporator coil being too close to the very large oil furnace heat exchanger.

With the DX coil set perhaps illegally close to the heat exchanger thus causing an airflow restrictions and wicked turbulence, a few of the coil's circuits may be unevenly heatloaded. Since the liquid refrigerant is not completely evaporated it will cause the outlet line that the TXV sensor bulb is on to be too cold and the TEV will shut-down the refrigerant flow, which can greatly reduce the BTUH capacity of the DX coil and the entire system.

Additionally, the return air intake should be at the ceiling level, in order to properly heat load the evaporator coil. Old gravity flow supply registers should be converted to diffusers, in order to achieve the proper air throw across the room. To achieve maximum airflow efficiency, --the supply air and return air ductwork must be properly sized, along with oversizing the filter grille areas.

  ===============
One Performance Assessment research revealed:
Several recurring factors were found to account for the inadequate flows:

    * Return ducts and return grills were often undersized
    * Fans were set to medium rather than high speed for cooling operation
    * Filters and cooling coils were dirty with high flow resistance
    * Duct system static pressures were elevated due to circuitous runs, pinched ducts, turbulence, etc.
    * Larger outdoor units were installed without changing the indoor unit. (Wow!)
    * Devices had been added which increased system static pressures.

On piston refrigerant control systems, they may flood back liquid which could damage the compressor, unless the system is way under-charge. Thermo Pride could install airflow turning vanes just above the heat exchanger to funnel the air directly into the DX coil, instead of most of the airflow hitting the bottom of the DX's drain pan causing extreme back-pressure/turbulence and an imbalanced DX coil circuitry heatload!

Static regain explained: every time the velocity is reduced there is a conversion to static pressure. In this case, it not only loses all of the velocity airflow energy due to hitting the heat exchanger , furnace side walls, and evaporator drain pan, which also skyrockets static pressure, greatly reducing the blower's ability to deliver the required CFM!

The required main trunk Supply Air velocity is lost between the heat exchanger and the evaporator drain pan, and therefore there is insufficient velocity and static pressure at the Supply Air diffusers to deliver the throw and requisite CFM!

Darrell Udelhoven 

------------- 
  • Clean the furnace flue pipe, barometric damper and chimney base.
  • Check the condition of the furnace heat exchanger.

  • Use brushes and a vacuum cleaner to remove soot buildup from the heat exchanger cavities inside the furnace. Use extra long heat exchanger brushes of the correct diameter and a shop vac with a ten foot long & one inch diameter hose, to remove soot buildup from Thermo Pride OL11 heat exchanger cavities. These are difficult to reach in many oil furnaces, and it takes patience and perseverance to do a good job. (Extremely Important for safe performance and efficiency!)

  • Oil Furnace Heat Exchanger Soot Cleanout

  • Contractor's Servicing Oil Furnace's Sooted Heat Exchangers
"Getting it RIGHT, makes all the difference in the world."
-------------------------------------------------------------------

DISCLAIMER:
Any of the HVAC companies I list on any of my web pages have nothing to do with the information I post on any of my Web pages nor do I assume any responsibility for how anyone uses that information.
All HVAC/R work should always be done by a licensed Contractor! This information is only placed on these pages for your understanding & communication with contractors & techs.

This information is for the edification of contractors and techs. I am NOT liable for your screw-ups, you are liable for what you do! - Darrell Udelhoven

Darrell's Refrigeration Heating and Air Conditioning - Federal Refrigerant Licensed - Retired Licensed Contractor

Please write me if you have anything you'd like to contribute! - Darrell 

Click here to tell a friend about this Web site

Please feel free to link your web pages to any of mine.

Easy Check of the Actual BTUH Performance of your AC

Optimizing an Air Conditioner's EER Performance and Output  Save on Energy Costs!        

Air Conditioning EER Levels & Evaporator Air Flow
Even your new AC Unit 'could be' getting 40% less than its Rated BTUH-
See the Field Tests- & Reasons

An Air Conditioning and Heating Efficiency Check Up - Contractor New

  MY GLOBAL ECONOMIC Policy PEOPLE EMPOWERMENT PAGES

  HVAC-TALK Forum

Darrell Udelhoven - udarrell

Empowerment Communications
Covering The Real Political Issues
Posted: 01/28/04; Edited: 07/30/07