|
We could
cut
residential heating and cooling equipment size in America by 30% to 50%
if
Contractor's would perform Home
Energy Audits to reduce Manual J
heat-gain heat-loss calculations and provide
full
credit for every load reducing element or detail they can use when
doing
the
calculation audits.
Load reduction remedial actions should always be provided as options toward further reducing Air Conditioning and heating equipment sizing. The Proper Sizing of Equipment, and Duct Sealing with Proper Airflow CFM will greatly reduce cooling costs! Is your Heat pump or AC 30 to 50% Over Sized? -------------------------- Local Contractor Locater Map - Talk with These Forum Contractor PROs in your area CFM & FPM Velocity Sizing MERV 8 Pleaded Filters 1” deep M-8 filter’s rated at 175 fpm medium and 350 fpm high; A 16X20 1" MERV 8, Rated @ only 780-CFM Heat Pump Trouble Shooting Diagnostics An overview of avoidable errors: First, there has to be a 75 to 100-psig pressure differential between head & suction for the reversing valve to function. Second, systems must have a proper refrigerant charge for the reversing valve to function properly. In cooler weather the outdoor condenser must be blocked off with plastic on the inlet to achieve 110-F condensing temperature. The solenoid valve is easy to trouble shoot. It has two vent lines to each end of the reversing valve & an equalizer line connected to the compressor suction line. (More soon.) The TXV's ball check valve at the outside coil sticks in the closed position: system will operate okay in heating mode, as it's supposed to be closed; in cooling mode, low head & suction will occur. The outdoor check-valve sticks open, the system will operate normally in cooling mode, it's supposed to be open but not in heating mode. You should always have with you a powerful magnet on an extension rod to reach into plenum's to free up stuck check valves. A TXV power element losing its charge will starve the evaporator coil, because pressure on top of the valve is an opening force. Trouble Shooting TXVs .pdf I will list the easy ways to trouble shoot heat pumps; but I have carpal tunnel & have to type with eraser ends of pencils, so will continue ASAP... come back later to see my easy heat pump diagnostic methods. I redo other pages, which saves typing! *Basics Featuring the Testo 556 -Video of a very thorough Air Conditioning Testing setupThe Testo 416 Airflow Test Checking airflow must be performed before charging a systemMore HVAC Videos at the bottom of this & other pages ================================================================================ Contractors' should use the equipment manufacturers blower data and the Manual D procedures to find the room cubic feet per minute (CFM) airflow values and then use published performance data to select the appropriate sized Supply-Air outlet & Return-Air ducting & grilles, type and size, for each room. There also should be a low resistance return air path for every room that has a supply outlet, door undercuts are borderline acceptable. Manual D procedures should be used to size all the duct runs, - and systems should comply with ASHRAE standards; completely seal all runs located in an unconditioned space and insulate these runs to preferably R-8. Contractor's should Certify the work they have done, i.e., —measured all air flows, balanced the air distribution system and then used certified protocols (superheat & Subcooling) to check and balance the refrigerant charge. After all the installation work has been done, the Operating Performance Standard Data of the operating System should be Certified by the contractor. This should Include the static pressure readings, CFM of the system airflow, air temperature rise across the condensing coils, and the entire performance data. Provide your customers with more than they paid for and you will have more business and solid referrals. ----------------------------------------------------------------------------- Because
the new high Seer efficiency air conditioners “have a smaller tonnage
compressor” for their capacity rating, then do the lower SEER rated
units that are being replaced. Therefore, the ultra high SEER units do
not achieve as high an the indoor temp-split. The older lower SEER
units could achieve a 4 to 6-F lower evaporator coil temp under the
same indoor conditions. The colder coil of the lower SEER units did a
better job of removing humidity under some indoor conditions. Measuring Low Airflow
I normally would measure the airflow with a flow hood, also called a capture hood. You should normally have around 400 CFM (Cubic Feet per Minute) per ton of cooling. Half of the systems I measure have [a mere] 200 CFM per ton, OR LESS. This will be aggravated by a dirty air filter, Some Restrictive high efficiency air filter's or grilles closed in rooms that you are not using. Normally, do not turn the thermostat down below 70º [74º 76º -better] degrees. A/C Tech guru, 'Stretch' If you can't afford a flow hood, also called a capture hood, then buy an anemometer & do the math.Get a low cost Testo Tester & ballpark
figure actual BTUH & EER - the information on it: http://www.amazon.com/Crosse-Technol.../dp/B0002WZRKE Also, get a low-cost digital flat-headed pocket Thermometer to use flat on the piping; these test instruments will PAY big returns! ----------- This should be helpful: (Edited 6/15/10) Take the Supply Air & Return Air wet bulb temperatures & interpose them on the enthalpy chart linked below. Duct system CFM X* 4.5 @sea-level, or use X* 4.35 if 1000' above sea-level, X* change in enthalpy = BTUH (Ballpark) Operating Performance. "U Must Right Click Link & open in New Tab," look-up wet bulb enthalpy figures on chart," & figure enthalpy change. Wet Bulb Enthalpy Chart Rules of Thumb for Duct Systems - Hart&Cooley DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS http://www.dca.state.ga.us/development/constructioncodes/publications/1ONE.pdf Look at the ducting, if it is not to code; make hard copies of this code & give it to whoever does the ducting work Make sure they redo it right! Never have flex duct interiors commercially cleaned, I just viewed Home Inspection photos showing the interior damaged & insulation plugging the duct. Home Inspectors warn people because the duct cleaner's tell them it won't damage the ducts. Some HI's look into the boot areas for clues of problems... ============================================================= First,
before doing
anything
else check the sizing, and thoroughly seal and properly insulate all
the ductwork!
|
||||||||||||||||||
|
Summer Comfort Zone |
||
|
Relative
Humidity |
Maximum
Comfortable Temperature |
Minimum
Comfortable Temperature |
|
60% |
78.5oF |
72.5oF |
|
50% |
79ºF |
73ºF |
|
40% |
79.5oF |
73.5oF |
|
30% |
80oF |
74oF |
The above comfort zone was found to be acceptable to 90% of test subjects drawn from a range of age groups and genders, with work and life-styles involving varying levels of activity and clothing. An air conditioning system that establishes and maintains indoor conditions within this zone will provide thermal comfort. It will produce a neutral sensation, occupants will feel neither too hot nor too cold. Above chart and findings From: Home Energy Magazine Online September/October 1996) Sizing Air Conditioners: If Bigger Is Not Better, What Is? by John Proctor and Peggy Albright Toward Optimal Occupant Comfort
If
you over pay for over capacity equipment, --you will be paying more
every month and will not be as comfortable as you would sizing it right
to also achieve the appropriate humidity levels!
When a typical HVAC contractor quotes the efficiency of the Air
Conditioning equipment's SEER & Btu/hr, and leads you to believe
the new equipment will automatically deliver that SEER efficiency &
Btu/hr rating, think again. Typically, --installed equipment only
operates at 55% to 70% of rated capacity. Oversized equipment is the
worst combination there is because the duct system airflow and heatload
on the cooling coil are often way off what is required!
Equipment Ratings are only the 'potential efficiency' of that component of the system under perfect conditions." Over half of the system's efficiency depends on correct equipment sizing toward adequate run-time, on the duct system sizing, i.e., on the quality of the complete field-installation!
What you want & need is right sized equipment operating at its optimal ratings within varying conditions, for your optimal comfort and savings.
If all contractor's would do the above, coupled with installing equipment sized according Manual J loads (with no safety factor), along with Manual S selection procedures, comfort would go up, humidity control would improve, and installation and operating costs would be much lower.Especially
if your system is oversized or there are a lot of low AC load days use
an adjustable differential room TH.
TH
Differential: Differential is defined as
the difference between the cut-in and cut-out
points as
However, the nominal BTU/hr rating of some range from 36,000 down to around 34,000-BTU/hr.
Additionally, with high indoor temperatures & very high humidity a nominal 36,000-BTU/hr could go considerably higher.
Example, Goodman Expanded Data: a 3-ton condenser 13-SEER
GSC130363A, with a 4-ton evaporator coil:
1434-cfm or 478-cfm per ton of cooling
85 OAT Outdoor Ambient Temp
80 IDB Indoor Dry Bulb
71 IWB Indoor Wet Bulb or 63% Relative Humidity
Nominal BTU/hr of 39,500
At 75 OAT outdoor Ambient Temp
other figures the same, nominal listed @ 40,500-BTU/hr. (At ARI
Conditions)
Moderate
outdoor temps coupled with high indoor temps results in a high latent
humidity
heatload through the evaporator coil which boils refrigerant at its
fastest
rate, which transfers more heat outdoors per unit of time.
- udarrell
------------------------------------
That is why we should NOT be upsizing equipment for latent heat
removal; because
the A/C system increases its latent capacity to handle that load. When
the unit is upsized the run-time operating-cycles can be way too short
for effective latent heat
(humidity) removal.
Do your own figuring based on this formula. Get the Motor Power Factors (PF) of the compressor and fan motor from the manufacturers.
CONDENSER TEMP-SPLITS - Comfortmaker® 12-SEER units - used 0.88 Motor Power Factors
2-Ton 24,800 22-F T.-Split Cond. CFM 1400 WATTS 2659http://www.udarrell.com/air_return_latent_condenser_split.jpg IE Browser's
2.5-T 30,200 20-F Temp-S Cond. CFM 2000 WATTS 3404
3-Ton 35,600 17-F Temp-S Cond. CFM 2800 WATTS 4107
3.5 T 42,500 19-F Temp-S Cond. CFM 2800 WATTS 4554
4-Ton 48,500 18.5-F Temp-S Cond. CFM 3400 WATTS 4761
5-Ton 59,000 23-F Temp-S Cond. CFM 3400 WATTS 6969
The new Goodman 13-SEER 1½-Ton Condenser, 2-Ton Evaporator:
At 675-cfm 450-per/ton cooling | 85-F ODB | 63-IWB | 52% RH | 20-F ID Delta T | 18,600-Btuh
201-psig 100-F = 15-F cond. temp split - larger coil areas | 80-psig suction
=================================================================
The
Base Spec sheets
12-SEER
part no. 421 41 33301 03, Feb 2001. These are the Comfortmaker®
units, which are nearly identical to Heil® units. I used
the first rating on each tonnage class. While the "Performance Cooling
Data" is listed at a 95-F outside ambient temperature, you
can adjust the indoor airflow to get the Nominal BTUH Rating at the
customer's normal indoor stat' temp' setting, and the most outside
temperature/degree
operating hours.
Take
the "listed watts" of the compressor and Condenser fan and multiply
that wattage by 0.85 X's 3.413
to get the BTUH heat additive of the
motor then add the listed BTUH of the condenser to it, and then divide
by the condenser fan's CFM.
By
using
the various units' "base specification sheet data" from the
dealer,
you can determine if it is operating near its BTUH capacity rating. Some
packaged units run a very
high condenser discharge CFM airflow
Have
a manual J heat load
done and consider slightly undersizing a replacement condenser.
If you have an older furnace, there may not be enough airflow through the evaporator coil.
Have all of the ductwork, diffusers, return-air grilles and filter areas checked and properly sized, the ductwork must be properly sealed.
In cold climate, consider replacing the furnace with a new high efficiency condenser furnace.
Then
replace the central A/C
system using a TEV refrigerant control on the evaporator.
By slightly undersizing the condenser and making certain you have an
optimal and balanced heatload on the cooling coil during normal
run-time conditions, —the unit will have a much greater BTU/hr heat
transfer output during average run-time conditions!
Air
Temperature Drop
Through Evaporator Coil (1987 Period)
Indoor
temperature
and humidity load variations graph.
Refrigeration
&
Air-Conditioning (ARI) Second Edition,
Page 624, ©
1987
Getting
it right makes all the difference in the world.
DISCLAIMER:
I
do NOT
assume any responsibility for how anyone uses the information on my Web
pages.
All HVAC/R work should always be done by a licensed Contractor! This
information is only placed on these pages for your understanding &
communication with contractors & techs.
This
information is for the edification of contractors and techs. I am NOT liable for what you do,
you are liable for what you do! - Darrell Udelhoven
|
Please write me if you have anything you'd like to contribute! - Darrell |
Let's All Save Energy! Please feel free to link your web pages to any of mine.Click here to tell a friend about this Web site Let's All Save Energy!
#1 HVAC Talk Community - Jason
Hughes Construction - "Roofing"
- Free Estimates SW WI
(608) 574-0769 (Best Price Best Work!)MY GLOBAL ECONOMIC POLICY PEOPLE EMPOWERMENT PAGES
Darrell
Udelhoven - udarrell
Empowerment
Communications
Covering
The Real Political Issues
Posted:
11/03/11