HEAT PUMP TROUBLE SHOOTING DIAGNOSTICS 

with Darrell Udelhoven Home Plus HVAC Efficiency Overview Audio Refers to my linked duct sizing pages

We could cut residential heating and cooling equipment size in America by 30% to 50% if Contractor's would perform Home Energy Audits to reduce Manual J heat-gain heat-loss calculations and provide full credit for every load reducing element or detail they can use when doing the calculation audits.

Load reduction remedial actions should always be provided as options toward further reducing Air Conditioning and heating equipment sizing.

The Proper Sizing of Equipment, and Duct Sealing with Proper Airflow CFM will greatly reduce cooling costs!
Is your Heat pump or AC 30 to 50% Over Sized?

--------------------------
Local Contractor Locater Map - Talk with These Forum Contractor PROs in your area
CFM & FPM Velocity Sizing MERV 8 Pleaded Filters 
1” deep M-8 filter’s rated at 175 fpm medium and 350 fpm high; A 16X20 1" MERV 8, Rated @ only 780-CFM
Heat Pump Trouble Shooting Diagnostics
An overview of avoidable errors:
First, there has to be a 75 to 100-psig pressure differential between head & suction for the reversing valve to function.
Second, systems must have a proper refrigerant charge for the reversing valve to function properly.

In cooler weather the outdoor condenser must be blocked off with plastic on the inlet to achieve 110-F condensing temperature.

The solenoid valve is easy to trouble shoot.
It has two vent lines to each end of the reversing valve & an equalizer line connected to the compressor suction line. (More soon.)

The TXV's ball check valve at the outside coil
sticks in the closed position: system will operate okay in heating mode, as it's supposed to be closed; in cooling mode, low head & suction will occur.

The outdoor check-valve sticks open, the system will operate normally in cooling mode, it's supposed to be open but not in heating mode.

You should always have with you a powerful magnet on an extension rod to reach into plenum's to free up stuck check valves.

A TXV power element losing its charge will starve the evaporator coil, because pressure on top of the valve is an opening force.
Trouble Shooting TXVs .pdf

I will list the easy ways to trouble shoot heat pumps; but I have carpal tunnel & have to type with eraser ends of pencils, so will continue ASAP... come back later to see my easy heat pump diagnostic methods. I redo other pages, which saves typing!

*Basics Featuring the Testo 556 -Video of a very thorough Air Conditioning Testing setup

The Testo 416 Airflow Test Checking airflow must be performed before charging a system
More HVAC Videos at the bottom of this & other pages

================================================================================


Contractors' should use the equipment manufacturers blower data and the Manual D procedures to find the room cubic feet per minute (CFM) airflow values and then use published performance data to select the appropriate sized Supply-Air outlet & Return-Air ducting & grilles, type and size, for each room. There also should be a low resistance return air path for every room that has a supply outlet, door undercuts are borderline acceptable.


Manual D procedures should be used to size all the duct runs, - and systems should comply with ASHRAE standards; completely seal all runs located in an unconditioned space and insulate these runs to preferably R-8.

Contractor's should Certify the work they have done, i.e., —measured all air flows, balanced the air distribution system and then used certified protocols (superheat & Subcooling) to check and balance the refrigerant charge. After all the installation work has been done, the Operating Performance Standard Data of the operating System should be Certified by the contractor. This should Include the static pressure readings, CFM of the system airflow, air temperature rise across the condensing coils, and the entire performance data. Provide your customers with more than they paid for and you will have more business and solid referrals.
-----------------------------------------------------------------------------

Because the new high Seer efficiency air conditioners “have a smaller tonnage compressor” for their capacity rating, then do the lower SEER rated units that are being replaced. Therefore, the ultra high SEER units do not achieve as high an the indoor temp-split. The older lower SEER units could achieve a 4 to 6-F lower evaporator coil temp under the same indoor conditions. The colder coil of the lower SEER units did a better job of removing humidity under some indoor conditions.

Instead of doing things that would reduce the heat-gain/heat-loss, I tend to believe that they look at the capacity of the installed unit and then up the tonnage one-half to a full-ton, perhaps because they are concerned about the smaller compressor per tonnage rating handling a high heat-load.

Far too many unknown realities need to be exposed in order to size the new equipment at the proper tonnage. For example, the ductwork system may not be up to "Manual D standards." If the cubic feet for minute airflow were to fall below 325-CFM per-ton, the unit will not deliver anywhere near its rated capacity.

If the original installation was not done properly, the unit will not perform to its full capacity.
The  home's heat-gain/heat-loss should be reduced using all the methods that will produce a reasonable payback. Then a heat load Calc manual J. should be done, after which, a manual at us for equipment sizing should be done.

If you want optimal seer ratings performance is better to slightly undersized the equipment than do oversized it. The reason for this is the slight undersizing will reduce the frequency of the on-off cycling of the condenser, which is a major factor in the (SEER) “Seasonal Energy Efficiency Rating.”

Low energy usage 20” floor fans will keep you comfortable even with a two to three or more temperature differential spread. The longer run cycles are terrific for reducing humidity.

Another way to improve the SEER ratings performance is to install a digital thermostat with adjustable differential temperature set-point, which can be set to reduce the number of on/off cycles per hour, per day and per cooling season. Additionally, a variable speed blower/air handler and a time delay blower relay will also improve the SEER.

There are too high a percentage of systems that have improperly insulated, sized, & leaky ductwork with inadequate airflow, which leads to an improperly charged system, which causes extremely poor performance and very high utility bills.

Measuring Low Airflow

I normally would measure the airflow with a flow hood, also called a capture hood. You should normally have around 400 CFM (Cubic Feet per Minute) per ton of cooling. Half of the systems I measure have [a mere] 200 CFM per ton, OR LESS. This will be aggravated by a dirty air filter, Some Restrictive high efficiency air filter's or grilles closed in rooms that you are not using. Normally, do not turn the thermostat down below 70º  [74º 76º -better] degrees. A/C Tech guru, 'Stretch'

If you can't afford a flow hood, also called a capture hood, then buy an anemometer & do the math.

Get a low cost Testo Tester & ballpark figure actual BTUH & EER - the information on it:
http://www.amazon.com/Testo-605-H2-H.../dp/B000774B6A

Everyone, very low cost anemometer to get airflow FPM Velocities, get it:
http://www.amazon.com/Crosse-Technol.../dp/B0002WZRKE

Also, get a low-cost digital flat-headed pocket Thermometer to use flat on the piping; these test instruments will PAY big returns!
-----------
This should be helpful: (Edited 6/15/10)
Take the Supply Air & Return Air wet bulb temperatures & interpose them on the enthalpy chart linked below.
Duct system CFM X* 4.5 @sea-level, or use X* 4.35 if 1000' above sea-level, X* change in enthalpy = BTUH (Ballpark) Operating Performance.
"U Must Right Click Link & open in New Tab," look-up wet bulb enthalpy figures on chart," & figure enthalpy change.
Wet Bulb Enthalpy Chart
Rules of Thumb for Duct Systems  - Hart&Cooley
DESIGN AND INSTALLATION OF RESIDENTIAL FLEXIBLE DUCTWORK SYSTEMS
http://www.dca.state.ga.us/development/constructioncodes/publications/1ONE.pdf

Look at the ducting, if it is not to code; make hard copies of this code & give it to whoever does the ducting work
Make sure they redo it right!
Never have flex duct interiors commercially cleaned, I just viewed Home Inspection photos showing the interior damaged & insulation plugging the duct.
Home Inspectors warn people because the duct cleaner's tell them it won't damage the ducts. Some HI's look into the boot areas for clues of problems...

=============================================================

First, before doing anything else check the sizing, and thoroughly seal and properly insulate all the ductwork!

Design Engineering and Installation Objectives should be focused towards achieving the most efficient and effective means toward  a conditioned space that is within the "Human Comfort Zone, and within an affordable investment 'payback' period." 

Summer Comfort Zone

Relative Humidity

Maximum Comfortable Temperature

Minimum Comfortable Temperature

60%

78.5oF

 72.5oF

50%

79º

73ºF

40%

79.5oF

  73.5oF

30%

80oF

74oF

The above comfort zone was found to be acceptable to 90% of test subjects drawn from a range of age groups and genders, with work and life-styles involving varying levels of activity and clothing. An air conditioning system that establishes and maintains indoor conditions within this zone will provide thermal comfort. It will produce a neutral sensation, occupants will feel neither too hot nor too cold. Above chart and findings From: Home Energy Magazine Online September/October 1996) Sizing Air Conditioners: If Bigger Is Not Better, What Is?  by John Proctor and Peggy Albright  Toward Optimal Occupant Comfort 

If you over pay for over capacity equipment, --you will be paying more every month and will not be as comfortable as you would sizing it right to also achieve the appropriate humidity levels!

When a typical HVAC contractor quotes the efficiency of the Air Conditioning equipment's SEER & Btu/hr, and leads you to believe the new equipment will automatically deliver that SEER efficiency & Btu/hr rating, think again. Typically, --installed equipment only operates at 55% to 70% of rated capacity. Oversized equipment is the worst combination there is because the duct system airflow and heatload on the cooling coil are often way off what is required!

Equipment Ratings are only the 'potential efficiency' of that component of the system under perfect conditions." Over half of the system's efficiency depends on correct equipment sizing toward adequate run-time, on the duct system sizing, i.e., on the quality of the complete field-installation!

What you want & need is right sized equipment operating at its optimal ratings within varying conditions, for your optimal comfort and savings.

If all contractor's would do the above, coupled with installing equipment sized according Manual J loads (with no safety factor), along with Manual S selection procedures, comfort would go up, humidity control would improve, and installation and operating costs would be much lower.

Utility demand loads could be cut by at least a third, or even up to a half. Energy loads would be significantly reduced, reducing our nation's energy usage. The return on the time and effort invested on this higher quality level of work would be tremendous - for customers, the community and the nation.

Unfortunately, most HVAC contractors don't use these procedures to size equipment and design duct systems. It's estimated that only 10% of heating and cooling equipment sizing decisions are based on some type of Manual J calculation and that less than 1% of the jobs are based on an aggressive accurate implementation of these recommended design procedures.

Many if not most contractors are designing new and replacement systems that feature oversized equipment, "improperly sized supply outlets" and duct runs that are too small, too leaky and inadequately insulated.

The Manual J gives appropriate answers if you use an “aggressive” set of assumptions. However, most HVAC contractors tend to skew input data to make the calculations match their favorite rules of thumb. Follow the manual J rules and you will get a reasonable margin of safety. However, after skewing the numbers, many contractors throw in an extra half ton or more of A/C to feel safe. No wonder a large percentage of equipment is considerably oversized. Also, the airflow is usually so compromised on the oversized units that it isn't putting out many more btuh than properly sized equipment would be, but it's an energy waster and is costing and arm and leg to operate.

Especially if your system is oversized or there are a lot of low AC load days use an adjustable differential room TH.
TH Differential
: Differential is defined as the difference between the cut-in and cut-out points as measured at the thermostat under specified operating conditions. For example, if the thermostat turns the COOLING EQUIPMENT ON AT 78-F & OFF at 76-F that is a 2 degree differential setting; heating equipment on at 70 degrees F and turns the heating equipment off at 74 degrees F, then the differential is 4 degrees F. Some have half degree increment settings over several degrees of differential spread.

For example, in Rockford, IL a 2,400 sq./ft home with 600 sq./ft of window area, it figures to take 4 tons or so to cool it. However, a 2-Ton Unit moving 1,000-CFM of air (or 500-cfm per ton of cooling), even at 95 degrees with a blazing sun heat outside and very high humidity the 2-ton cooling equipment system still cycles! It is very comfortable at around 75-F and 50% Relative Humidity.

There's a 2400 sq./ft home in Lancaster (SW WI)and one I know of in Ohio, cooling the homes to very comfortable levels using 2-ton A/C systems.

Okay, with 8 foot ceilings, 19200 cu ft air volume at 1000-cfm that's 60000 cu ft per hour, or just over 3 air changes per hour, with the added long run times to reduce humidity. Would you rather have the costly oversized 4 Ton Unit?

Perhaps the Manual J could be improved; however, if used with "integrity" it can deliver good results. However, contractors that don't want to size according to an honest manual J calculation simply change some of the inputs to make the procedure deliver answers they feel safe with, and, --they are never challenged.

First, you need a tight, well insulated building with good windows. Then you need to make sure the person performing the load calculations uses accurate information, and doesn't “fudge or skew the numbers." After they have the equipment sizing answer, "they must be certain the ductwork is properly sized, sealed and well insulated." It's not rocket science and it is time all Contractors are held to a new set of codes and ethical standards.

Take the condenser entering air temp and leaving air temp, subtract for the temp-split. As a double verification:You can use the high-side (SCT) Saturated Condensing Temperature minus the outdoors-ambient temperature; the difference gives you the condenser temperature-rise or temperature/split. There is NO excuse for not utilizing this important diagnostic check. Always use an accurate volt meter and amprobe to make sure you are not overloading the compressor's Wattage Service Factor and check the compressor discharge line to see that it is under 225-F.

CONDENSER TEMP-SPLITS - My Brother's Heil 12-SEER Condensing Unit
1½-Ton - Rated at 18,400-BTUH,  Condenser fan CFM 1400 (Total Cond. Watts 2221 X's power Factors 0.85 X's= 1887 X's * 3.413 = 6,443-BTUH Motor Heat additive +18400= Motor Power "Rated Gross Heat Ejection" is 24,843-BTUH / 1400= 17.7-F  = 17.5-F Temp Rise Cond/Split. His condenser only gets a 10 to 12 temp rise split, the evaporator appears to be under heat-loaded or, an unbalanced heatload on the DX coil's circuits.

  The new Goodman 13-SEER 1½ Ton Condenser, 2-Ton Evaporator:
At 675-cfm 450-per/ton cooling | 85-F ODB | 63-IWB | 52% RH | 20-F ID Delta T | 18,600-Btuh
201-psig 100-F = 15-F cond. temp split - larger coil areas | 80-psig suction


The probable cause is "an unbalanced airflow heatload through the evaporator coil. "It's a (Thermo Pride OL 11 oil furnace). Those oil furnaces have a very large round heat exchanger that goes to near the top of the furnace, --due to a low basement ceiling the DX coil sets perhaps illegally close to the heat exchanger causing a few of the coil's circuits to be under heatloaded. Since the liquid refrigerant is not completely evaporated it will cause the outlet line that the TEV sensor bulb is on to be too cold and the TEV will shut-down the flow, which greatly reduces the BTUH capacity of the DX coil and the system. On piston refrigerant control systems, they may flood back liquid which could damage the compressor, unless the system is way under-charged. Thermo Pride could install airflow turning vanes just above the heat exchanger to funnel the air directly into the DX coil, instead of most of the airflow hitting the bottom of the DX's drain pan turbulence back-pressure and an imbalanced DX coil circuitry heatload!

Many DX coils are delivering half to a ton less btuh than the rating of the condenser. Either remedy the problems or install a smaller condenser sized to the achievable DX coil's nominal heat transfer limits.

There is more to the "System Btu/hr Capacity Ratings," than I have clear answers for at this time.
What is included or excluded in the capacity ratings in respect to motor heat Btu/hr that does nothing to reduce the total heatload of the conditioned air. Motor heat is a factor to be dealt with, perhaps more so on the smaller units.
-----------------------------
Some of the high SEER units do not look so great when you figure their EER.
However, when selecting A/C equipment between EER Verses SEER:
"How many hours (yes hours) your area spends close (or above a 60% duty cycle) to OD design temp, determines which rating method you should use." - Beenthere

--------------------------------
My response to an HVAC Forum question on BTU & Tonnage Ratings:
Three ton is 36,000 BTUs.
The units are Rated in Nominal Tons per hour.

However, the nominal BTU/hr rating of some range from 36,000 down to around 34,000-BTU/hr.

Additionally, with high indoor temperatures & very high humidity a nominal 36,000-BTU/hr could go considerably higher.

Example, Goodman Expanded Data: a 3-ton condenser 13-SEER GSC130363A, with a 4-ton evaporator coil:
1434-cfm or 478-cfm per ton of cooling
85 OAT Outdoor Ambient Temp
80 IDB Indoor Dry Bulb
71 IWB Indoor Wet Bulb or 63% Relative Humidity
Nominal BTU/hr of 39,500
At 75 OAT outdoor Ambient Temp
other figures the same, nominal listed @ 40,500-BTU/hr. (At ARI Conditions)

Moderate outdoor temps coupled with high indoor temps results in a high latent humidity heatload through the evaporator coil which boils refrigerant at its fastest rate, which transfers more heat outdoors per unit of time.
- udarrell
------------------------------------
That is why we should NOT be upsizing equipment for latent heat removal; because the A/C system increases its latent capacity to handle that load. When the unit is upsized the run-time operating-cycles can be way too short for effective latent heat (humidity) removal.

The chart split listed below is at Condenser Design conditions: Indoor Return Air 80-F dry bulb 67-F Wet Bulb or 50% Relative Humidity as you go up to 99% RH the condenser split could increase by up to 6-F; down as much as 4-F at a low humidity of 55-F Wet Bulb.

Do your own figuring based on this formula. Motor BTU/hr additive = Watts X's PF x's 3.413 for Btu/Watts additive added to rated BTUH, divided by condenser fan CFM X's 1.08 =  condenser Temp-Split. Get the Motor Power Factors (PF) of the compressor and fan motor from the manufacturers. Some of the temp-split figures need correcting, will do ASAP. Some Splits rounded.
Do your own figuring based on this formula. Get the Motor Power Factors (PF) of the compressor and fan motor from the manufacturers.

CONDENSER TEMP-SPLITS - Comfortmaker® 12-SEER units - used 0.88 Motor Power Factors
-Ton 18,000-Btu/hr 20-F Cond. Split |1400-CFM| WATTS (1591x 0.88-MPF=1432x3.413 = 4,382+18000 = 22,382/1400 = 15.987x1.08 = 17.26-F Condenser Temp split. TXV Metering device, - changed the equation.
2-Ton  24,800  22-F T.-Split    Cond. CFM 1400     WATTS 2659
2.5-T  30,200  20-F Temp-S    Cond. CFM 2000     WATTS 3404
3-Ton  35,600  17-F Temp-S   Cond. CFM 2800     WATTS 4107
3.5 T  42,500  19-F Temp-S    Cond. CFM 2800     WATTS 4554
4-Ton  48,500  18.5-F Temp-S Cond. CFM 3400     WATTS 4761
5-Ton  59,000  23-F Temp-S    Cond. CFM 3400     WATTS 6969

The new Goodman 13-SEER 1½-Ton Condenser, 2-Ton Evaporator:
At 675-cfm 450-per/ton cooling | 85-F ODB | 63-IWB | 52% RH | 20-F ID Delta T | 18,600-Btuh
201-psig 100-F = 15-F cond. temp split - larger coil areas | 80-psig suction

=================================================================
http://www.udarrell.com/air_return_latent_condenser_split.jpg IE Browser's
Page 618, Refrigeration & Air-Conditioning (ARI) Second Edition, © 1987
Those lower SEER units had higher condenser splits than 12-SEER and higher units.
Sorry, I defiled the graph, 90-db outdoor, 80-db indoors with 67 wet bulb/50% RH represents the condenser splits shown above. (Always, check voltage and amp draw!)

The Base Spec sheets 12-SEER part no. 421 41 33301 03, Feb 2001. These are the Comfortmaker® units, which are nearly identical to Heil® units. I used the first rating on each tonnage class. While the "Performance Cooling Data" is listed at a 95-F outside ambient temperature, you can adjust the indoor airflow to get the Nominal BTUH Rating at the customer's normal indoor stat' temp' setting, and the most outside temperature/degree operating hours.

Take the "listed watts" of the compressor and Condenser fan and multiply that wattage by 0.85 X's 3.413 to get the BTUH heat additive of the motor then add the listed BTUH of the condenser to it, and then divide by the condenser fan's CFM.

By using the various units' "base specification sheet data" from the dealer, you can determine if it is operating near its BTUH capacity rating. Some packaged units run a very high condenser discharge CFM airflow

Like to lower your Air Conditioning Utility Bills?

Look at all the ways you can to reduce the heat and humidity load, caulk, weather-strip, and insulate, to keep the heat and humidity outside.

Have a manual J heat load done and consider slightly undersizing a replacement condenser.

If you have an older furnace, there may not be enough airflow through the evaporator coil.

Have all of the ductwork, diffusers, return-air grilles and filter areas checked and properly sized, the ductwork must be properly sealed.

In cold climate, consider replacing the furnace with a new high efficiency condenser furnace.

Then replace the central A/C system using a TEV refrigerant control on the evaporator.

By slightly undersizing the condenser and making certain you have an optimal and balanced heatload on the cooling coil during normal run-time conditions, —the unit will have a much greater BTU/hr heat transfer output during average run-time conditions!

With a properly sized system and proper evaporator airflow you will have consistent optimal nominal capacity heat absorption and removal, coupled with longer run-time cycles.

I believe that optimal efficiencies, with variable latent/sensible heat loads, could be effectively achieved through the use of computerized control system components.

http://www.udarrell.com/air_temperature_drop_evaporator.jpg

Air Temperature Drop Through Evaporator Coil (1987 Period)
Indoor temperature and humidity load variations graph.
Refrigeration & Air-Conditioning (ARI) Second Edition,
Page 624, © 1987

Getting it right makes all the difference in the world.

Proper Sizing of Residential Heating & Air Conditioning Ductwork Systems

====================== 

DISCLAIMER:

I do NOT assume any responsibility for how anyone uses the information on my Web pages.
All HVAC/R work should always be done by a licensed Contractor! This information is only placed on these pages for your understanding & communication with contractors & techs.

This information is for the edification of contractors and techs. I am NOT liable for what you do, you are liable for what you do!  - Darrell Udelhoven

Darrell's Refrigeration Heating and Air Conditioning - Federal Refrigerant Licensed - Retired Licensed Contractor

Please write me if you have anything you'd like to contribute! - Darrell 

Click here to tell a friend about this Web site Let's All Save Energy!

 Let's All Save Energy! Please feel free to link your web pages to any of mine.
Customers -Simple Check!
Contractors Up-Sizing High SEER Equipment
TH Differential  Ratings 

  • MY HVAC BLOG - YOUR QUESTIONS & COMMENTS WELCOME New 7/12/08
  • ac-trouble-shooting-chart.html
  • AC Superheat and Subcooling   
  • The Air Side of Air Conditioning - Static Pressure 

  • Excessive Airflow coupled with an Excessive Charge will greatly reduce AC capacity
  • Air Conditioning SEER Levels & Evaporator Air Flow - Are you losing 15 to 40% under SEER Rating?

    SEER Payback is NOT being Properly Represented to the Consumers

  • Determining Your Air Conditioner's Actual BTUH Capacity Output 

  • Proper Sizing of Residential Heating & Air Conditioning Ductwork Systems
  • Air Conditioning Engineered for Latent Heat Removal  For high humidity climates
  • Air Conditioning Contractors  Discussion Sizing SEER EER Latent Heat 
  • An Air Conditioning and Heating Efficiency Check Up - Contractor

  • Air Conditioning Maximum Efficiency - Check-Up  Get your A/C optimized for efficiency
  • Air Conditioning - Latent Heat Removal  Comfort-Zone Efficiency
  • FINDING the LATENT HEAT of CONDENSATION of Your Air Conditioner
  • Optimizing Room Air Conditioner's EER     
  • OIL HEATING AIRFLOW TEST  Using Thermometers
    MY HVAC BLOG - YOUR QUESTIONS & COMMENTS WELCOME
    Easy Ways to Cut Your Energy Use in Half New

       HVAC TALK #1 HVAC Talk Community - Jason Hughes Construction - "Roofing" - Free Estimates SW WI (608) 574-0769 (Best Price Best Work!)
    GARDEN WEB - Heating & Air Conditioning Forum - New
    DIY Do It Yourself Forum  - "Do It Yourself" TV - New
    DIY FORUM RULES - "Do It Yourself, - Forum Rules" - New

    MY HVAC BLOG - YOUR QUESTIONS & COMMENTS WELCOME New 7/12/08
    Follow me on Twitter All about Reducing Energy Costs - New

    *Video checking static ESP *Video 2 checking static ESP View! I Got DSL 11/2010

    Air Flow CFM of a very large Supply Air Register using a Testo 410 Vane Anemometer  Basic...

    *Video measuring airflow Velocity W/ anemometer on a Return Air grille
    I'd use close to .50% for the free-area of a clean FILTER, & .90% factor for open grille area. He programmed it in, because when I did the math using .90% for the grille I got 336.57863-FPM Vel *X 2.376562-SF free-air-area= 799.9-CFM, or 2-Ton of airflow.

    *Basics Featuring the Testo 556 - Video of a very thorough Air Conditioning Testing setup 2/26/11

    Realtime HVAC A/C BTUH Performance Output (Part 1 of 2) YouTube Video

    *Realtime HVAC A/C BTUH Performance Output (Part 2 of 2) YouTube Video


    - EMPOWERMENT COMMUNICATIONS
    -----------------------------------------------------------------------------------------------

      MY GLOBAL ECONOMIC POLICY PEOPLE EMPOWERMENT PAGES

    Darrell Udelhoven - udarrell
    Empowerment Communications
    Covering The Real Political Issues
    Posted: 11/03/11