Air Conditioning System Sizing for Optimal EER & SEER Efficiency

The Proper Sizing of Equipment, and Duct Sealing with Proper Airflow CFM will greatly reduce cooling costs!

 Design Engineering Ojectives | TH Differential | Equipment Ratings  | Determining System's Metering Device
  | CONDENSER TEMP SPLITS |  Is your AC 30 to 50% Oversized?   - with Darrell Udelhoven - HVAC RETIRED - udarrell
We could cut residential heating and cooling equipment size in America by 30% to 50% if Contractor's would perform honest Manual J calculations and provided full credit for every load reducing element or detail they can when doing the calculation audit. Additionally, load reduction remedial actions should be provided as options toward further reducing Air Conditioning and heating equipment sizing.

Down sizing has many advantages; the existing duct system & air handler will function more efficiently helping to achieve the unit's nominal tonnage capacity with less than peak heatload conditions. That improves EER & SEER performance.

Contractors' should use the equipment manufacturers blower data and the Manual D procedures to find the room cubic feet per minute (CFM) airflow values and then use published performance data to select the appropriate sized supply air outlet, type and size, for each room. There also should be a low resistance return air path for every room that has a supply outlet, door undercuts are borderline acceptable.

Manual D procedures should be used to size all the duct runs, and systems should comply with ASHRAE standards; completely seal all runs located in an unconditioned space and insulate these runs to preferably R-8.

Contractor's should Certify the work they have done, i.e., —measured all air flows, balanced the air distribution system and then used certified protocols to check and balance the refrigerant charge. After all the installation work has been done, the Operating Performance Standard Data of the operating System should be Certified by the contractor. This should Include the static pressure readings, CFM of the system airflow, air temperature rise across the condensing coils, and the entire performance data. Provide your customers with more than they paid for and you will have more business and solid referrals.

Measuring Low Airflow

I normally would measure the airflow with a flow hood, also called a capture hood. You should normally have around 400 CFM (Cubic Feet per Minute) per ton of cooling. Half of the systems I measure have [a mere] 200 CFM per ton, OR LESS. This will be aggravated by a dirty air filter, Some Restrictive high efficiency air filter's or grilles closed in rooms that you are not using. Normally, do not turn the thermostat down below 70º  [74º 76º -better] degrees. says A/C Tech guru, 'Stretch'

First, before doing anything else check the sizing, and thoroughly seal and properly insulate all the ductwork!

Design Engineering and Installation Objectives should be focused towards achieving the most efficient and effective means toward  a conditioned space that is within the "Human Comfort Zone, and within an affordable investment 'payback' period." 

Summer Comfort Zone

Relative Humidity

Maximum Comfortable Temperature

Minimum Comfortable Temperature

60%

78.5oF

 72.5oF

50%

79oF

73oF

40%

79.5oF

  73.5oF

30%

80oF

74oF

The above comfort zone was found to be acceptable to 90% of test subjects drawn from a range of age groups and genders, with work and life-styles involving varying levels of activity and clothing. An air conditioning system that establishes and maintains indoor conditions within this zone will provide thermal comfort. It will produce a neutral sensation, occupants will feel neither too hot nor too cold. Above chart and findings From: Home Energy Magazine Online September/October 1996) Sizing Air Conditioners: If Bigger Is Not Better, What Is?  by John Proctor and Peggy Albright  Toward Optimal Occupant Comfort 

If you over pay for over capacity equipment, --you will be paying more every month and will not be as comfortable as you would sizing it right to also achieve the appropriate humidity levels!

EER
7 EER or less
8 EER
9 EER
10 EER
12 EER
13 EER
'Max' condenser air temp 'delta-T'
30
27
24
15 to 25
14 to 24
ave. less
Max temp drop 'across' E-Coil
20
22
24
26
ave. more
ave. more
'Max' SA/Return Entering Air 'Delta-T'
35
32
29
27
ave. less
ave. less
The Supply Air & the Entering Return Air delta-T, - tends towards less & less as the EER goes higher,
therefore, dehumidification could become more difficult at the highest EER levels. The EER & SEER levels widen, as SEER sky rockets.

When a typical HVAC contractor quotes the efficiency of the Air Conditioning equipment's SEER & Btu/hr, and leads you to believe the new equipment will automatically deliver that SEER efficiency & Btu/hr rating, think again. Typically, --installed equipment only operates at 55% to 70% of rated capacity. Oversized equipment is the worst combination there is because the duct system airflow and heatload on the cooling coil are often way off what is required!

Equipment Ratings are only the 'potential efficiency' of that component of the system under perfect conditions." Over half of the system's efficiency depends on correct equipment sizing toward adequate run-time, on the duct system sizing, i.e., on the quality of the complete field-installation!

What you want & need is right sized equipment operating at its optimal ratings within varying conditions, for your optimal comfort and savings.

If all contractor's would do the above, coupled with installing equipment sized according Manual J loads (with no safety factor), along with Manual S selection procedures, comfort would go up, humidity control would improve, and installation and operating costs would be much lower.

Utility demand loads could be cut by at least a third, or even up to a half. Energy loads would be significantly reduced, reducing our nation's energy usage. The return on the time and effort invested on this higher quality level of work would be tremendous - for customers, the community and the nation.

Unfortunately, most HVAC contractors don't use these procedures to size equipment and design duct systems. It's estimated that only 10% of heating and cooling equipment sizing decisions are based on some type of Manual J calculation and that less than 1% of the jobs are based on an aggressive accurate implementation of these recommended design procedures.

Many if not most contractors are designing new and replacement systems that feature oversized equipment, "improperly sized supply outlets" and duct runs that are too small, too leaky and inadequately insulated.

The Manual J gives appropriate answers if you use an “aggressive” set of assumptions. However, most HVAC contractors tend to skew input data to make the calculations match their favorite rules of thumb. Follow the manual J rules and you will get a reasonable margin of safety. However, after skewing the numbers, many contractors throw in an extra half ton or more of A/C to feel safe. No wonder a large percentage of equipment is considerably oversized. Also, the airflow is usually so compromised on the oversized units that it isn't putting out many more btuh than properly sized equipment would be, but it's an energy waster and is costing and arm and leg to operate.

Especially if your system is oversized or there are a lot of low AC load days use an adjustable differential room TH.
TH Differential
: Differential is defined as the difference between the cut-in and cut-out points as measured at the thermostat under specified operating conditions. For example, if the thermostat turns the COOLING EQUIPMENT ON AT 78-F & OFF at 76-F that is a 2 degree differential setting; heating equipment on at 70 degrees F and turns the heating equipment off at 74 degrees F, then the differential is 4 degrees F. Some have half degree increment settings over several degrees of differential spread.

For example, in Rockford, IL a 2,400 sq./ft home with 600 sq./ft of window area, it figures to take 4 tons or so to cool it. However, a 2-Ton Unit moving 1,000-CFM of air (or 500-cfm per ton of cooling), even at 95 degrees with a blazing sun heat outside and very high humidity the 2-ton cooling equipment system still cycles! It is very comfortable at around 75-F and 50% Relative Humidity.

There's a 2400 sq./ft home in Lancaster (SW WI) and one I know of in Ohio, cooling the homes to very comfortable levels using 2-ton A/C systems.

Okay, with 8 foot ceilings, 19200 cu ft air volume at 1000-cfm that's 60000 cu ft per hour, or just over 3 air changes per hour, with the added long run times to reduce humidity. Would you rather have the costly oversized 4 Ton Unit?

Perhaps the Manual J could be improved; however, if used with "integrity" it can deliver good results. However, contractors that don't want to size according to an honest manual J calculation simply change some of the inputs to make the procedure deliver answers they feel safe with, and, --they are never challenged.

First, you need a tight, well insulated building with good windows. Then you need to make sure the person performing the load calculations uses accurate information, and doesn't “fudge or skew the numbers." After they have the equipment sizing answer, "they must be certain the ductwork is properly sized, sealed and well insulated." It's not rocket science and it is time all Contractors are held to a new set of codes and ethical standards.

Take the condenser entering air temp and leaving air temp, subtract for the temp-split. As a double varification: You can use the high-side (SCT) Saturated Condensing Temperature minus the outdoors-ambient temperature; the difference gives you the condenser temperature-rise or temperature/split. There is NO excuse for not utilizing this important diagnostic check. Always use an accurate volt meter and amprobe to make sure you are not overloading the compressor's Wattage Service Factor and check the compressor discharge line to see that it is under 225-F.

CONDENSER TEMP-SPLITS - My Brother's Heil 12-SEER Condensing Unit
1.5-Ton - Rated at 18,400-BTUH,  Condenser fan CFM 1400 (Total Cond. Watts 2221 X's power Factors 0.85 X's= 1887 X's * 3.413 = 6,443-BTUH Motor Heat additive +18400= Motor Power "Rated Gross Heat Ejection" is 24,843-BTUH / 1400= 17.7-F  = 17.5-F Temp Rise Cond/Split. His condenser only gets a 10 to 12 temp rise split, the evaporator appears to be under heat-loaded or, an unbalanced heatload on the DX coil's circuits.

 
The new Goodman 13-SEER 1.5-Ton Condenser, 2-Ton Evaporator:
At 675-cfm 450-per/ton cooling | 85-F ODB | 63-IWB | 52% RH | 20-F ID Delta T | 18,600-Btuh
201-psig 100-F = 15-F cond. temp split - larger coil areas | 80-psig suction


The probable cause is "an unbalanced airflow heatload through the evaporator coil. "It's a (Thermo Pride OL 11 oil furnace). Those oil furnaces have a very large round heat exchanger that goes to near the top of the furnace, --due to a low basement ceiling the DX coil sets perhaps illegally close to the heat exchanger causing a few of the coil's circuits to be under heatloaded. Since the liquid refrigerant is not completely evaporated it will cause the outlet line that the TXV sensor bulb is on to be too cold and the TXV will shut-down the flow, which greatly reduces the BTUH capacity of the DX coil and the system. On piston refrigerant control systems, they may flood back liquid which could damage the compressor, unless the system is way under-charged. Thermo Pride could install airflow turning vanes just above the heat exchanger to funnel the air directly into the DX coil, instead of most of the airflow hitting the bottom of the DX's drain-pan turbulence back-pressure and an imbalanced DX coil circuitry heatload!

Many DX coils are delivering half to a ton less btuh than the rating of the condenser. Either remedy the problems or install a smaller condenser sized to the achievable DX coil's heat transfer limits.

What is included or excluded in the capacity ratings in respect to motor heat Btu/hr that does nothing to reduce the total heatload of the conditioned air. Motor heat is a factor to be dealt with, perhaps more so on the smaller units.

Finding out which metering device the system has without physically looking.

If you do not know whether the metering device is a TXV or orifice? 
Hook up your manifold gauges, block off considerable condenser air intake. If the suction pressure starts rising, you have a piston, or a cap tube.
If only the high side goes up, you have a TXV.

If it is a piston, get the CFM airflow correct first, then use the superheat method to charge it.
If it is a TXV, subcooling is the way to charge it, but check the Superheat to verify the TXV is holding within specs.
Normally plus or minus 3-degrees is acceptable for Subcooling, i.e., SC Target of 12 +/- 3 = 15 or 9-F SC.
--------------------------------------------
Do your own figuring based on this formula. Get the Motor Power Factors (PF) of the compressor and fan motor from the manufacturers.

CONDENSER TEMP-SPLITS
12-SEER units - Comfortmaker® | Heil® | Temp Star®  - used 0.88 Motor Power Factors
1.5-Ton 18,000  21-F Split       Cond. CFM 1400      WATTS 1536 1.5-Ton is from actual published DATA - ARI Rating Conditions
2-Ton  24,800  23-F T.-Split     Cond. CFM 1400     WATTS 2659
2.5-T  30,200  20-F Temp-S    Cond. CFM 2000     WATTS 3404
3-Ton  35,600  17-F Temp-S    Cond. CFM 2800     WATTS 4107
3.5 T  42,500  19-F Temp-S    Cond. CFM 2800     WATTS 4554
4-Ton  48,500  18.5-F Temp-S  Cond. CFM 3400   WATTS 4761
5-Ton  59,000  23-F Temp-S    Cond. CFM 3400    WATTS 6969

The new Goodman 13-SEER 1.5-Ton Condenser, 2-Ton Evaporator:
At 675-cfm 450-per/ton cooling | 85-F ODB | 63-IWB | 52% RH | 20-F ID Delta T | 18,600-Btuh
201-psig 100-F = 15-F cond. temp split - smaller capacity compressor to larger coil areas | 80-psig suction

=================================================================
http://www.udarrell.com/air_return_latent_condenser_split.jpg IE Browser's
Page 618, Refrigeration & Air-Conditioning (ARI) Second Edition, © 1987
Those lower SEER units had higher condenser splits than 12-SEER and higher units.
Sorry, I defiled the graph, 90-db outdoor, 80-db indoors with 67 wet bulb/50% RH represents the condenser splits shown above. (Always, check voltage and amp draw!)

The Base Spec sheets 12-SEER part no. 421 41 33301 03, Feb 2001. These are the Comfortmaker® units, which are nearly identical to Heil® units. I used the first rating on each tonnage class. While the "Performance Cooling Data" is listed at a 95-F outside ambient temperature, you can adjust the indoor airflow to get the Nominal BTUH Rating at the customer's normal indoor stat' temp' setting, and the most outside temperature/degree operating hours.

Take the "listed watts" of the compressor and Condenser fan and multiply that wattage by 0.85 X's 3.413 to get the BTUH heat additive of the motor then add the listed BTUH of the condenser to it, and then divide by the condenser fan's CFM.

By using the various units' "base specification sheet data" from the dealer, you can determine if it is operating near its BTUH capacity rating. Some packaged units run a very high condenser discharge CFM airflow

Like to lower your Air Conditioning Utility Bills?

Look at all the ways you can to reduce the heat and humidity load: caulk, weather-strip, insulate, radiant barriers, to keep the heat and humidity outside.

Have a manual J heat-load calc done, and in humid climates, consider slightly undersizing a replacement condenser.

If you have an older furnace, there may not be enough airflow through the evaporator coil.

Have all of the ductwork, diffusers, return-air grilles and filter areas checked and properly sized, the ductwork must be properly sealed.

In cold climate, consider replacing the furnace with a new high efficiency condenser furnace.

Then replace the central A/C system, Go for a scroll compressor & a TXV refrigerant control on the evaporator.

By slightly undersizing the condenser and making certain you have an optimal and balanced heatload on the cooling coil during normal run-time conditions, —the unit will have a much greater BTU/hr heat transfer output during average run-time conditions!

With a properly sized system and 450-CFM per/ton of cooling going through the evaporator coil, you will have consistent optimal nominal-capacity heat absorption, coupled with longer run-time cycles for optimal humidity control.

I believe that optimal efficiencies, with variable latent/sensible ratio heatloads, could be effectively achieved through the use of computerized control system components.

http://www.udarrell.com/air_temperature_drop_evaporator.jpg

Air Temperature Drop Through Evaporator Coil (1987 Period)
Indoor temperature and humidity load variations graph.
Refrigeration & Air-Conditioning (ARI) Second Edition,
Page 624, © 1987

Getting it right makes all the difference in the world.

Proper Sizing of Residential Heating & Air Conditioning Ductwork Systems 

============================
DISCLAIMER:

I do NOT assume any responsibility for how anyone uses the information on my Web pages.
All HVAC/R work should always be done by a licensed Contractor! This information is only placed on these pages for your understanding & communication with contractors & techs.

This information is for the edification of contractors and techs. I am NOT liable for what you do, you are liable for what you do!  - Darrell Udelhoven

Darrell's Refrigeration Heating and Air Conditioning - Federal Refrigerant Licensed - Retired Licensed Contractor

 

Please write me if you have anything you'd like to contribute! - Darrell 

Click here to tell a friend about this Web site Let's All Save Energy!

Please feel free to link to any of my web pages
.  
  • ac-trouble-shooting-chart.html
     
  • AC Superheat and Subcooling   

  • The Air Side of Air Conditioning - Static Pressure 
     
  • Excessive Airflow coupled with an Excessive Charge will greatly reduce AC capacity
  • Air Conditioning SEER Levels & Evaporator Air Flow - Are you losing 15 to 40% under SEER Rating?

  • SEER Payback is NOT being Properly Represented to the Consumers
  • Determining Your Air Conditioner's Actual BTUH Capacity Output 
  • Proper Sizing of Residential Heating & Air Conditioning Ductwork Systems
    Air Conditioning Engineered for Latent Heat Removal  For high humidity climates

  • Air Conditioning Contractors  Discussion Sizing SEER EER Latent Heat 

  • An Air Conditioning and Heating Efficiency Check Up - Contractor

  • Air Conditioning Maximum Efficiency - Check-Up  Get your A/C optimized for efficiency

  • Air Conditioning - Latent Heat Removal  Comfort-Zone Efficiency

  • FINDING the LATENT HEAT of CONDENSATION of Your Air Conditioner

  • Optimizing Room Air Conditioner's EER     
  • OIL HEATING AIRFLOW TEST  Using Thermometers Remodeling News Magazine 

  •    HVAC TALK #1 HVAC Talk Community
    HVAC Discussions The Official Mike Holmes Fan Forum - New
    GARDEN WEB - Heating & Air Conditioning Forum - New

    DIY Do It Yourself Forum  - "Do It Yourself" TV - New

    - EMPOWERMENT COMMUNICATIONS
    -----------------------------------------------------------------------------------------------

      MY GLOBAL ECONOMIC POLICY PEOPLE EMPOWERMENT PAGES

    Darrell Udelhoven - udarrell
    Empowerment Communications
    Covering The Real Political Issues
    Posted: 10/16/03; Edited: 06/24/08