An example of a 3.5-Ton air-conditioning system  delivering less than 1.5-Ton of Capacity

with Darrell Udelhoven (U-dl-hoven)

Gurgling Pulsating Sounds at TXV 

An example of a poor performing larger residential air-conditioning system in a new four year old home - AIR-CONDITIONER RUNNING TOO MUCH
3.5-Ton system delivering less than 1.5-Ton of capacity

Technician: I get this call from a Home Owner selling the home, that the home inspector says the delta-T (temperature drop or split) across the indoor evaporator coil is not in the 15-18 degree range.
So I get there and it is a 1900 sq. ft. home with a
3.5-ton 10-SEER Goodman. House is only 4 years old.

Here are the Tech's readings:

Ambient Temperature = 78-F

Suction Pressure = 70-
PSIG

R-22 Refrigerant = 41-F Suction Saturation Temperature (SST)

Or, 20-F Superheat (High) 

Suction Temperature
= 61-F Superheat -F

Head Pressure = 225-
PSIG
or, 109-F minus the104-F Liquid Line

That Is only 5–F Subcooling (Low) - (Darrell)
Liquid Line temperature= 104-F

“If Superheat is high and Sub-Cooling is low:
Charge must be adjusted. "System is undercharged."

Entering Dry Bulb= 74-F

Entering Wet Bulb= 64.5-F

Leaving DB= 66-F

Leaving WB= 61-F


Tech: I am at a loss for the 8 degree (register temperature drop (Delta-T).

"The Home Owner has never said house does not cool well -- just runs quite a bit when above 88 degrees."

Coils, ductwork, blower, etc., checks OK.

Tech: If I plug these numbers in my psychometric calculator (which by the way works very well) I get these numbers:

17203 "total" BTU/hr (heat removal)

13306 BTU/hr Sensible  BTU/hr (heat removal)

3717 BTU/hr latent 
BTU/hr (heat removal)

Tech: What is up?

================

Of course, you can get the delta-T in the lower end of the range by reducing airflow; which he did just so it would pass the home sale inspection.

"A lot more testing data was needed for a thorough diagnosis."

Here is only the Sub Cooling and Super Heat diagnosis:

It indicated 20 degrees Superheat with ambient temperatures between 75 and 85 should be 12 to 15 degrees, and 5-F Sub-Cooling that should be 12 to 15 degrees
.

Possible Diagnosis using Superheat and Sub-Cooling:

If Superheat is high and Sub-Cooling is low:
Charge must be adjusted. "System is undercharged."


If superheat is low and sub-cooling is high:
Charge must be adjusted. "System is overcharged."


If Superheat is high and Sub-Cooling is high:
"Could have blockage in coil, orifice, or line set."


If Superheat is low and Sub-Cooling is low:
"Piston orifice could be too big, there is no orifice in the unit or the orifice is stuck, or in backwards, and refrigerant is bypassing It."


If I were buying the home, I would ask for a full disclosure on all of the energy usage appliances, water heater, and especially the HVAC system. A full, truthful, accurate report on the HVAC system including the ductwork should be made available to potential buyers.
=========================

Gurgling Pulsating Sounds at TXV:Low evaporator heat-loads lead to reduced liquid line mass and increased evaporator mass could be due to airflow problems. Eliminate low evaporator heat-loads before looking into adjusting the refrigerant charge.  Gurgling and pulsation noises at the expansion device can be caused by low evaporator circuit heat-loads, low charge, and/or non-condensibles and moisture in the system. Unbalanced airflow through the various distributor circuits of the evaporator coil will cause the TEV to close down refrigerant flow starving the coil. Piston-flow-rators will make it impossible to properly charge the system and cooling will be greatly compromised unless you eliminate the cause! "Put your ear on the liquid line at the evaporator coil."

On every Rheem condenser cover it lists "non-condensibles and or moisture" as causes for a gurgling or pulsating noise at the expansion device. The entire evaporator circuits, may not become active for various reasons, - "the entire coil must become fully active for efficient performance."

The purpose of these recommendations is to provide liquid refrigerant at the expansion device and provide efficient operation. Hopefully, this will aid your research.  If I can be of additional assistance, contact me.
-----------------------------------------------------------

I estimate over 90% do not properly purge & evacuate contaminated central air conditioning systems.

The Triple Evacuation Method is normally done on central air conditioning systems:

First, remove any valve cores with a special  valve core remover this will speed up the evacuation time. Back service valves two turns off their back seat.

1) Re-claim unit charge (Recover all the refrigerant)


2) Charge system to 150 PSIG with dry nitrogen and leak test

3) On contaminated systems replace the filter dryers. Then Repair all leak(s)

4) Evacuate system to 500 microns valve off & see if it holds 500 microns for ten minutes, if it holds, break the vacuum with dry nitrogen

5) Evacuate system to a deeper 300 microns, valve off vac pump, & again break the vacuum with dry nitrogen

6) Evacuate system to 300 microns and charge unit (Recharge with fresh clean refrigerant)

7) Check to see if the Supply and Return air ducts were correctly sized & sealed by the original installer.

The “micron” is a metric unit of measure for distance. The micron is a unit of linear measure; one micron equals 1/25,400ths of an inch. Modern high capacity vacuum pumps help speed up the evacuation process.

===============

For many good reasons, Inspectors' need to get very tough on homes and commercial buildings that are being sold.

http://www.udarrell.com/ac-trouble-shooting-superheat-subcooling.html

http://www.udarrell.com/ac-trouble-shooting-chart.html
__________________
udarrell

The easy check is to add refrigerant until the suction superheat comes down, then recheck the temperatures and pressures and airflow through the evaporator coil, which should make for an easy diagnosis.

The pressures will indicate whether the compressor is okay, --it is possible that the system is imbalanced possibly due to, low evaporator heat loading, charge level, air in the refrigerant system, and/or wrong orifice size. (An oil-clogged system would be another factor to consider in inadequate evaporator loading providing similar conditions are found on a system.) 

c.) Higher than expected heat removal by the condenser is an evaporator too loaded up -- not a factor in this troubleshooting illustration. I'm including it to complete the possibilities for AC systems in general.

It's a good idea to check if the piston/orifice is correctly sized according to the manufacturer's literature. Charts for orifice size are only useful when you have the outdoor and indoor unit model numbers, --leaving supply duct problems or an overcharged system for these temp/pressure test results. The piston must be installed so that it seats and seals when te liquid flows against it otherwise the refrigerant will bypass the orifice hole!.

It is possible to find three or more things wrong on one system, which is what separates the real Techs from the dudes.

Normal Condenser Split for
10 SEER  3.5-ton A/C condenser can be, depending on its CFM, as high as 29ºF, 12-SEER would usually be between 20 to 24ºF  -- usually ends up about the manufacturer's design Condenser Delta T (Saturated Condenser Temp minus outdoor ambient).

Checking the condenser discharge air temperature split is an effective performance test measure that should be part of any maintenance check. Since there are no duct variables to contend with, the condenser is easy to inspect, thermometer calibration isn't an issue using the same thermometer for both in and out air, wet bulb temperature doesn't matter, and the compressor is closely matched to the condenser.

This is merely an illustration of some useful diagnostic procedures.
========
One Research Performance Assessment revealed:
Several recurring factors that accounted for inadequate flows:

    * Return ducts and return grills were often undersized
    * Blower Fan set to wrong speed for cooling operation
    * Filters blower wheel blades and cooling coils were dirty
    * Duct system static pressures were elevated due to circuitous runs, pinched ducts etc.
    * Larger outdoor units were installed without changing the indoor unit and duct system
    * Devices had been added which increased system static pressures.
 
Darrell Udelhoven 


Take the condenser entering air temp and leaving air temp, subtract for the temp-split. As a double verification: You can use the high-side (SCT) Saturated Condensing Temperature minus the outdoors-ambient temperature; the difference gives you the condenser temperature-rise or temperature/split. There is NO excuse for not utilizing this important diagnostic check. Always use an accurate volt meter and amprobe to make sure you are not overloading the compressor's Wattage Service Factor and check the compressor discharge line to see that it is under 225-F.

CONDENSER TEMP-SPLITS - My Brother's Heil 12-SEER Condensing Unit
1.5-Ton - Rated at 18,400-BTUH,  Condenser fan CFM 1400 (Total Cond. Watts 2221 X's power Factor 0.88 X's= 1955 X's * 3.413 = 6,673-BTUH Motor Heat +18400= Condenser's "Rated Gross Heat Ejection" is 25,073-BTUH / 1400= 17.9-F X's 1.08 = 19-F Temp Rise Cond/Split. His condenser only gets a 10 to 13 temp rise split, the evaporator appears to be under heat-loaded
or, an unbalanced heatload on the DX coil's circuitry.

The probable cause is "an unbalanced airflow heatload through the evaporator coil. "It's a (Thermo Pride OL 11 oil furnace). Those oil furnaces have a very large round heat exchanger that goes to near the top of the furnace, --due to a low basement ceiling the DX coil sets perhaps illegally close to the heat exchanger causing a few of the coil's circuits to be under heatloaded. Since the liquid refrigerant is not completely evaporated it will cause the outlet line that the TEV sensor bulb is on to be too cold and the TEV will shut-down the flow, which greatly reduces the BTUH capacity of the DX coil and the system. On piston refrigerant control systems, they may flood back liquid which could damage the compressor, unless the system is way under-charged. Thermo Pride could install airflow turning vanes just above the heat exchanger to funnel the air directly into the DX coil, instead of most of the airflow hitting the bottom of the DX's drain pan causing extreme turbulence back-pressure and an imbalanced DX coil circuitry heatload!

The chart split listed below is at Condenser Design conditions: Indoor Return Air 80-F dry bulb 67-F Wet Bulb or 50% Relative Humidity (RH) as you go up to 99% RH the condenser split could increase by up to 6-F; down as much as 4-F at a low humidity of 55-F Wet Bulb.

Do your own figuring based on this formula. Motor BTU/hr additive = Watts X's PF x's 3.413 for Btu/Watts additive added to rated BTUH, divided by condenser fan CFM X's 1.08 =  condenser Temp-Split. Get the Motor Power Factors (PF) of the compressor and fan motor from the manufacturers. (A 0.80 factor could be close.) Some of the temp-split figures need correcting, will do ASAP. Most Splits rounded off.

CONDENSER TEMP-SPLITS - Comfortmaker® 12-SEER units - used 0.80 Motor Power Factor

1.5 T  18,400   19 Split             Cond. CFM 1400     WATTS 2222
2-Ton  24,800  24-F Temp-S    Cond. CFM 1400     WATTS 2659
2.5-T  30,200  21-F Temp-S    Cond. CFM 2000     WATTS 3404
3-Ton  35,600  18-F Temp-S   Cond. CFM 2800     WATTS 4117
3.5 T  42,500  21-F Temp-S    Cond. CFM 2800     WATTS 4554
4-Ton  48,500  19.5-F Split      Cond. CFM 3400     WATTS 4761
5-Ton  59,000  25-F Temp-S    Cond. CFM 3400     WATTS 6969

Air Return - Latent Condenser Split

Page 618, Refrigeration & Air-Conditioning (ARI) Second Edition, C 1987
Those lower SEER units had higher condenser splits than 12-SEER and higher units.
Sorry, I defiled the graph, 90-db outdoor, 80-db indoors with 67 wet bulb or 50% RH represents the condenser splits shown above.

The graph should use 78-F indoor dry bulb (DB) and show the correlative Relative Humidity (RH) to the Wet Bulb (WB)-F readings. Equipment owners could then use an accurate Relative Humidity indicator so they could perform the temperature split diagnosis. Graphs would be specific to the equipment. Condenser CFM should be shown on the metal equipment specification tag and in all spec literature and in the home owners manual.


The condenser fan speeds are slower on several of the 10-SEER Tonnage Models. We are only trying to get a figure to go by for a comparison. When new condensers and Evaporator-coils "are installed on older air handlers" the new, or old, evaporator coils are usually under heat-loaded.

The Base Spec sheets 12-SEER part no. 421 41 33301 03, Feb 2001. These are the Comfortmaker® units, which are nearly identical to Heil® units. [I used the first rating on each tonnage class.] While the "Performance Cooling Data" is listed at a 95-F outside ambient temperature, you can adjust the indoor airflow to get the Nominal BTUH Rating at the customer's normal indoor stat' temp' setting and the most outside temperature/degree operating hours. 

Take the "listed watts" of the compressor and Condenser fan and multiply that wattage by 3.413 to get the BTUH heat additive of the motor then add the listed BTUH of the condenser to it, and then divide by the condenser's CFM. I'm now using the altitude multiplier additive to the initial temp split figure, look up the additive for the height you are above sea level.

With a properly sized system and proper evaporator airflow you will have consistent optimal nominal capacity heat absorption and removal coupled with the requisite longer run-time cycles. I believe that optimal efficiencies, with variable latent/sensible heat loads, could be effectively achieved through the use of computerized control system components.

------------- 

Getting it right makes all the difference in the world.

In the Prairie du Chien Crawford county area Contact:
RICKLEFF PLUMBING HEATING & AIR CONDITIONING
PRAIRIE DU CHIEN, WI  http://www.heildlr.com/rickleff/

Darrell's Refrigeration Heating and Air Conditioning - Federal Refrigerant Licensed - Retired - Licensed Contractor
If you want to talk, I'm in the Lancaster, WI - Phone book - Beetown exchange.

To Contact me: udarrell@pcii.net

Please write me if you have anything you'd like to contribute! - Darrell 

Click here to tell a friend about this Web site

Please feel free to link your web pages to any of mine.
  • OIL HEATING AIRFLOW TEST  Using Thermometers - New!

  • Best Practices Guide for residential HVAC retrofit
  • New TEC Energy Conservation Testing TechnologiesNew!
  • Energy Star  New!

  • Send your residential air conditioning question to
     udarrell@pcii.net   

      
    MY GLOBAL ECONOMIC Policy PEOPLE EMPOWERMENT PAGES

    Darrell Udelhoven - udarrell
    Empowerment Communications
    Covering The Real Political Issues
    Posted: 08/13/05; Revised 04/14/06