>Darrell Cynergy Home HVAC Energy Raters
Listen While Reading|
Please Respond on my Blog; let me know if you can't post: Ballpark Checking A/C Performance Condenser Temp-Splits Knowing Operating Static Pressures | Room T-stat Differential | Selecting Correct CFM Fan Speeds | Gurgling sounds at TEV | Oil Furnace blower Graph Design Engineering | Determining which metering device TXV or Fixed Orifice | 50% Load HomeAir Leaks | R410a_Evacuation CFM & FPM Velocity Sizing MERV 8 Pleaded Filters 1” deep M-8 filter’s rated at 175 fpm medium and 350 fpm high; A 16X20 1" MERV 8, Rated @ only 780-CFM |
*HEAT PUMP DIAGNOSTICS*Basics Featuring the Testo 556 - Video of a very thorough Air Conditioning Testing setup 2/26/11A lot more HVAC Videos at bottom of pagesWhy Look at your Ducts (Leakage up-to 33% of cooling cost) when replacing your AC System; a must viewing: http://www.youtube.com/watch?v=IV0Rwv5gco4 |
|
California
Research Report on EER SEER pdf -
download
07/23/08, SEER Payback - cannot be accurately represented! HVAC-TALK General Discussions: Importance of Two-Way Communications with HVAC Customers - with Darrell Udelhoven - HVAC RETIRED - udarrell Always begin with a thorough Home Energy AUDIT that shows all the options for lowering the heat-gain & heat-loss, then after reducing air infiltration, etc., have a room by room manual J heatload calc performed. A reduction in equipment sizing will usually greatly improve the duct system performance. This
is where the greatest savings in both heating & cooling will
accrue; this will help in the down-sizing of
equipment. Then
do a manual J room by room heat-gain calc with the option shown so you
can do everything possible to reduce all sources of heat-gain &
heat-loss, greatly reducing both heat & cooling BTUH equipment
sizing. Before you do anything else, educate yourself enough to "ensure that you request the proper things be done in the proper order of sequence." Checking ductwork & Airflow Checking Static Pressures is Critically Important. As is knowing the operating feet per minute (FPM) velocity, the CFM & BTUH to each room along with the Total CFM airflow & BTUH. First, before doing anything else
check and thoroughly seal all the ductwork! For efficient
operation, always check
the return air temperature at the blower & at the Return Air
Grille(s)
INTRODUCTION TO TOTAL COOLING PERFORMANCE;
The
second
thing you must
do & know "before charging any system" is to establish
the proper
airflow and heatload through
the evaporator coil. |
|||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Summer Comfort Zone |
||
|
Relative
Humidity |
Maximum
Comfortable Temperature |
Minimum
Comfortable Temperature |
|
60% |
78.5oF |
72.5oF |
|
50% |
79oF |
73oF |
|
40% |
79.5oF |
73.5oF |
|
30% |
80oF |
74oF |
The above comfort zone was found to be acceptable to 90% of test subjects drawn from a range of age groups and genders, with work and life-styles involving varying levels of activity and clothing. An air conditioning system that establishes and maintains indoor conditions within this zone will provide thermal comfort. It will produce a neutral sensation, occupants will feel neither too hot nor too cold. Above chart and findings From: Home Energy Magazine Online September/October 1996) Sizing Air Conditioners: If Bigger Is Not Better, What Is? by John Proctor and Peggy Albright Toward Optimal Occupant Comfort
| SEER |
7
SEER or less |
8
SEER |
9
SEER |
10
SEER |
12
SEER |
13
SEER |
| 'Max' condenser air temp delta-T |
30 |
25 |
24 |
+23 |
21 |
<less |
| Max
temp spread 'across' E-Coil |
20 |
22 |
24 |
26 |
>more |
>more |
| 'Max' SA/Return Entering Air Delta-T |
33 |
30 |
26 |
23 |
19 |
<less |
====================
My Scan of My ThermoPride OL 11 "Oil
Furnace" Graphed
Blower-Curve-Chart
(Same as my brother's Oil furnace)
Thermopride
OL 11
Graph ipg
image - Thank you Dave Staso, CA. for
the better expandable image!
"After it loads Right click "Show Original Images" -
Move cursor arrow over graph - Click +
when 'over graph' for expanded image," then print on the highest
quality setting.
Notice at 700-RPM with a quarter 1/4HP motor, I checked his actual
airflow at less than 300-CFM (no appreciable duct air leaks). the graph
shows 5.24" SP.
Now, we switch to a 1/3HP motor @800-RPM, the graph shows 6.85" SP
& only 400-CFM, not nearly enough airflow for 1.5-Ton of cooling.
Therefore we have to raise the evaporator coil 6" above the furnace on
rails & then check the airflow. Eliminating that restriction using
a 1/3HP motor, hopefully that will be adequate at +800-rpm & say
+5.5" SP & +700-CFM. Formula: SP2= (SP2/SP1)2 X's SP1
Every
manufacturer should
furnish
blower curve charts with their units and also put them on the Internet
for
service
tech's to download and print. Also, air conditioning codes should be
updated
in respect to proper sizing of the duct work which must include all the
pressure inducing factors when sizing the supply and return ducts.
Also, illustrate best furnace to evaporator coil transitions,
especially on oil furnaces! You should always keep the ESP to
0.5" or mfg'ers listing.
Below is an example of this
problem with a (Thermo Pride OL 11 oil
furnace).
The
low airflow probable cause is
"an unbalanced airflow
heatload
through the evaporator coil,
along with what is known as "static regain," due to the evaporator coil
being too close to the large oil furnace heat exchanger.
Those oil furnaces have a very
large heat exchanger that goes to
near the top of the furnace, --due to a low basement ceiling the DX
coil
sets perhaps illegally close to the heat exchanger causing an airflow
restriction,
and a few of the
coil's circuits to be unevenly heatloaded.
Since the liquid refrigerant is
not completely evaporated it will cause the outlet line that the TEV
sensor
bulb is on, to be too cold and the TEV will shut-down the refrigerant
flow, which
greatly reduces the BTUH capacity of the DX coil and the system.
On piston refrigerant control
systems, they may flood back liquid which
could damage the compressor, unless the system is way under-charge.
Thermo
Pride could install airflow turning vanes just above the heat exchanger
to funnel the air directly into the DX coil, instead of most of the
airflow
hitting the bottom of the DX's drain
pan causing extreme back-pressure/turbulence and an imbalanced DX coil
circuitry heatload!
Static regain explained:
every time the velocity is reduced there is a conversion to static
pressure. In this case it not only loses all of the velocity airflow
energy due to hitting the evaporator drain pan, but also skyrockets
static pressure, greatly reducing the blower's ability to deliver the
required CFM!
The required main trunk Supply Air velocity and static pressure is lost between the heat exchanger and the evaporator drain pan, and therefore there is insufficient velocity and static pressure at the SA diffusers to deliver the throw and requisite CFM!
A starved evaporator
coil is a condition in which not enough refrigerant has been supplied
through
the total coil length. Therefore, expansion of the refrigerant has not
occurred through the whole coil length, resulting in too-low a heat
exchange
and lowered BTU/hr capacity operation.
Too many do not properly purge & evacuate contaminated central air conditioning systems.
The Triple Evacuation Method is normally done on refrigeration systems, R-410a systems require it on central air conditioning systems:A flooded evaporator
is the opposite of the starved coil. Using a Flow-rator Piston
refrigerant
control, too much refrigerant is passed through the evaporator coils,
resulting
in unevaporated liquid passing onto the suction line and an under
capacity
system.
http://www.udarrell.com/air_temperature_drop_evaporator.jpg
Air
Temperature Drop
Through Evaporator Coil (1987 Period)
"Indoor
temperature and humidity load variations graph."
Refrigeration
&
Air-Conditioning (ARI) Second Edition,
Page 624, ©
1987
Measuring Low Airflow
I normally would measure the airflow with a flow hood, also called a capture hood. You should normally have around 400 CFM (Cubic Feet per Minute) per ton of cooling. Half of the systems I measure have [a mere] 200 CFM per ton, OR LESS. This will be aggravated by a dirty air filter, Some Restrictive high efficiency air filter's or grilles closed in rooms that you are not using. Normally, do not turn the thermostat down below 70º [74º 76º -better] degrees. A/C Tech guru, 'Stretch' A/C OWNERS: Measuring the air temperature rise across the outdoor condenser coils is the easiest check point to determine the total amount of latent and sensible BTUH of heat your air-conditioner is actually transferring to the outside. You will enjoy doing it, doing it could lead to making changes that could considerably improve your Air Conditioning System's performance, thus improving your total comfort while in most cases greatly reducing your cooling bills. SEE CHARTS BELOW.
By way of background: ARI introduced the Energy Efficiency Ratio "EER" in 1975. This was an "HVAC" industry instituted and policed way "to determine the relative efficiencies" of one unit to another in the cooling mode. "EER" was determined by dividing the published steady state capacity by the published steady sate power input at 80°F dB/ 67°F Wb indoor and 95°F dB outdoor. This was quite objective yet unrealistic with respect to system "real world" operating conditions.
The SEER of a system is determined by multiplying the steady state Energy Efficiency Ratio (EER) measured at conditions of 82°F outdoor temperature, 80°F dB/ 67°F Wb indoor entering air temperature by the (run time) Part Load Factor (PLF) of the system. A major factor NOT considered, is the actual part loading factor of the indoor evaporator cooling coil, that greatly reduces the unit's listed btuh capacity and SEER efficiency level.
In
an oil furnace installation, a high static pressure can be
partially
due to the evaporator coil being installed too close to the big round
heat
exchanger. If you have room, a reducer transition should be stalled to
funnel the air into the aperture opening of the A coil.
Installing
the coil on to of the furnace can cause high turbulence and back
pressure, which
combined
with inadequate, (along with floor
level intake returns) ducting coupled with long runs and other
problems
could increase the static pressure so high that your blower motor's
HP will
not move enough heat loaded room air across the heat absorbing
evaporator
coils and fins to fully heat load the outside
condenser coil.
Floor
level supply and return air quadruples the
problem. External static pressures need to be kept within or below 0.5"
Water Column for efficient operation of the blower wheel design and
motor
HP.
A flow rator type metering device will continue to feed to much refrigerant into the coil which can cause it to drop below freezing temperatures which will block air flow and also can flood liquid back to the compressor causing severe damages to it. Additionally, the refrigerant charge will not be accurate unless it is weighed into the system. There can be NO accurate measure of Superheat without an optimally balanced heat load through all the evaporator coil circuits.
Take the condenser entering air temp and leaving air temp, subtract for the temp-split. As a double verification: You can use the high-side (SCT) Saturated Condensing Temperature minus the outdoors-ambient temperature; the difference gives you the condenser temperature-rise or Delta-T temperature/split. There is NO excuse for not utilizing this important diagnostic check. Always use an accurate volt meter and amprobe to make sure you are not overloading the compressor's Wattage Service Factor and check the compressor discharge line to see that it is under 225-F.
On wrap-around condenser coil top air discharge condensers' --first, check the condenser entering air dry-bulb temp., and the condenser dry-bulb discharge air temp., while moving the TH around in the air stream. (This will usually be around a 18 to 24 degree condenser temperature split rise. Older units run a higher temperature split.)
Techs should get the condenser air flow data in CFM from the manufacturer's data. Because all the heat discharged by the condenser air flow also includes the converted latent heat of the evaporator's absorbed condensation heat, you can determine the total BTUH of heat exhausted by the AC condenser and thus determine if it is getting anywhere near its BTUH rating. You also need to add the additive heat of the condenser's compressor and fan motor. The indoor blower motor is also a heat contributing factor, not figured in this formula.
You can make up the charts for 10, 12, and 14 SEER units for specific makes. One chart might include many different makes. The 14 SEER is a whole different bucket of bolts, as it uses a larger condenser and a very high CFM for a lower temp-split.
For the uninitiated, Delta-T is the difference between the air temperature entering and leaving the outdoor AC condensing unit. This is a good diagnostic check because it measures the latent heat of condensation as well as the sensible heat absorbed by the vaporizing refrigerant in the indoor evaporator coil. I'm betting when you find out approximately how many BTUH that the AC system is actually transferring outside, you may be shocked. Many new Packaged Units have a very high condenser CFM airflow and a LOW TEMPERATURE SPLIT! Very high SEER units have oversized condenser coils and very low temp-splits! To get the gross BTUH Heatload the Evaporator (DX) Coil is absorbing (which includes both latent, sensible heat) (These are ARI Formulas) There are many ways to figure the amount of heat the evaporator is transferring to the condenser.
First, determine the
Gross Rated BTUH the condenser is ejecting.
Condenser’s
Gross Btuh
= Condenser’s rated CFM X’s
Temp Split X’s
0.88
Brother’s
Example:
Heil, 1.5-ton, with 2-ton
DX (evaporator) coil with a TEV refrigerant control, -Condenser Rated
at
18,400-BTUH, with a 13-SEER rating.
1400-cfm X’s (13-temp rise X’s 1.08) = 19,656-Gross BTUH heat ejected, subtract the 6,562.5-btuh motor heat additive = only 13,093-NET BTUH transferred from the evaporator (DX) Coil to the condenser, compared to a net heat transfer rating of 18,400-btuh! A loss of 6,307-btuh or over half a ton loss, or over a one-third loss of heat transfer! A one ton condenser would have done almost as much! As the rooms cool it is only a 12-F temp-split or 11,582-btuh output! The actual lack of an adequate DX coil heatload would only require a small one-ton condenser!
CONDENSER TEMP-SPLITS
- My Brother's Heil 12-SEER Condensing Unit
1.5-Ton -
Rated at
18,400-BTUH, Condenser fan CFM 1400 (Total Cond. Watts 2221 X's
power Factors 0.88
X's= 1887 X's = 1954.48 * 3.413 = 6,670-BTUH Motor Heat additive
+18400= Motor Power
"Rated Gross Heat Ejection" is 25,070-BTUH / 1400 = 17.9-F
Temp Rise Cond/Split. The condenser only gets a 10 to 13-F
temp-rise-split,
depending on the heat load in the house. Supply air and return air are
both at the floor level recirculating the coldest air in the room to
the
DX coil, the evaporator is NOT being supplied with an adequate temp
split
heat load or, an unbalanced heatload on the DX coil's circuitry.
The probable cause is "an unbalanced airflow heatload through the evaporator coil. "It's a (Thermo Pride OL 11 oil furnace). Those oil furnaces have a very large round heat exchanger that goes to near the top of the furnace, --due to a low basement ceiling the DX coil sets perhaps illegally close to the heat exchanger causing a few of the coil's circuits to be under heatloaded. Since the liquid refrigerant is not completely evaporated it will cause the outlet line that the TEV sensor bulb is on to be too cold and the TEV will shut-down the flow, which greatly reduces the BTUH capacity of the DX coil and the system. On piston refrigerant control systems, they may flood back liquid which could damage the compressor, unless the system is way under-charge. Thermo Pride could install airflow turning vanes just above the heat exchanger to funnel the air directly into the DX coil, instead of most of the airflow hitting the bottom of the DX's drain pan causing extreme turbulence back-pressure and an imbalanced DX coil circuitry heatload!
The chart split listed below is at Condenser Design conditions: Indoor Return Air 80-F dry bulb 67-F Wet Bulb or 50% Relative Humidity as you go up to 99% RH the condenser split could increase by up to 6-F; down as much as 4-F at a low humidity of 55-F Wet Bulb.Do your own figuring based on this formula. Motor BTU/hr additive = Watts X's PF x's 3.413 for Btu/Watts additive added to rated BTUH, divided by condenser fan CFM X's 1.08 = condenser Temp-Split. Get the Motor Power Factors (PF) of the compressor and fan motor from the manufacturers. (A 0.80 factor could be close.) Some of the 10-SEER temp-split figures need correcting, will do ASAP. Most Splits rounded off.
Formula for finding CFM Airflow from Velocity in FPM
If you can measure the air velocity coming from a known size duct or open area of a SA register, here is a rough ballpark formula to get the CFM:
CFM = (velocity in (FPM) Feet per Minute times the Square Footage of the duct area). To convert sq.ins. multiply by 0.00694 for sq.ft., or divide sq.ins. by 144.
Converting square duct inches to round duct size, Figuring the Square Inches of Round Ducts, an 8" x 8" duct = 64-sq.ins. x .7854 = 50.26 sq. ins. You round off to 50 sq. ins. for an 8" duct. Or, simply getting the square inches of round ducts: a 7" duct; 7" x 7" = 49 x .7854 = 38.48-sq.ins. or divide / by 144 = .2672222-sq.ft. X's a velocity of 500-fpm = 133.6-cubic feet per minute delivered to the room; 133.6-cfm x 30 = 4,008-BTUH.
Sized for in the chart below - BTU/hr per CFM figures "are figured for heatpumps at 450-CFM per ton of cooling."
Use 800 to 900-FPM MAINS' VEL. Use an optimum of 500-FPM VEL for Supply Branch Runs | Air speed Face of Return.
Air Filter Rack Sizing
I realize this will never happen if you use the furnace filter size; however, Air Filter Rack Sizing for efficient operation - Size Gross Return Air filter grille area for 200-sq. ins. per ton. For a 5-Ton system, that would mean Two filter racks 25X20's each, I would go with Two 30X18" RA filter racks for 1080-sq.ins for a 5-Ton system.
http://www.udarrell.com/air_return_latent_condenser_split.jpg
Page 618,
Refrigeration
& Air-Conditioning (ARI) Second Edition, ©
1987
Those lower SEER
units
had higher condenser splits than 12-SEER and higher units.
Sorry, I defiled the
graph.
90-db outdoor, 80-db indoors with 67 wet bulb/50% RH
represents
the condenser splits shown above.
http://www.udarrell.com/air_temperature_drop_evaporator.jpg
Air
Temperature Drop
Through Evaporator Coil (1987 Period)
"Indoor
temperature and humidity latent load variations graph."
Refrigeration
&
Air-Conditioning (ARI) Second Edition,
Page 624, ©
1987
http://www.udarrell.com/air_return_latent_condenser_split.jpg
Page 618,
Refrigeration
& Air-Conditioning (ARI) Second Edition, ©
1987
Those lower SEER
units
had higher condenser splits than 12-SEER and higher units.
Sorry, I defiled the
graph.
90-db outdoor, 80-db indoors with 67 wet bulb/50% RH
represents
the condenser splits shown above.
http://www.udarrell.com/air_temperature_drop_evaporator.jpg
Air
Temperature Drop
Through Evaporator Coil (1987 Period)
"Indoor
temperature and humidity latent load variations graph."
Refrigeration
&
Air-Conditioning (ARI) Second Edition,
Page 624, ©
1987
-------------
As you put more total heat-load through the evaporator coil, up to its
capacity ceiling, both total capacity and efficiency increase for
optimal Btu/hr, EER, and SEER.
You can achieve a higher latent ratio in high humidity climates through
design changes, evaporator, and TXV metering device selection, set at
6º F for optimum reduction of the temperature of the DX Coil, and
reducing airflow after the unit gets the humidity near 50%. At the
higher humidity levels, the unit will operate closer to its Btu/hr
rating set at 400-cfm/ton. Using modern control systems, this would be
easy to achieve.
When we use to have an oversized compressor in relationship to the
evaporator's capacity, it could get that DX coil very cold in a hurry
and keep it that way.
Specially engineer-designed DX Coils could optimize total latent
capacity at the highest to below 50% relative humidity levels. Areas of
Florida, Louisiana and even Green Bay, WI need unit systems designed
for optimal latent heat operating capacities.
--------------
|
Typical
matched units from major manufacturers have Sensible Heat Ratios (SHR)
in the 68% to 80% range (or 32% to 20% Latent) when it is 95-F outside
and 75-F with 50% relative humidity inside. Proper mixing of the air
and
proper distribution to individual rooms is critical for comfort.
The condenser fan speeds are slower on several of the 10-SEER Tonnage Models. We are only trying to get a figure to go by for a comparison. When new condensers and Evaporator coils "are installed on older air handlers" the new, or old, evaporator coils are usually under heat-loaded. (Always, check voltage and amp draw!) The Base Spec sheets 12-SEER part no. 421 41 33301 03, Feb 2001. These are the Comfortmaker® units, which are nearly identical to Heil® units. I used the first rating on each tonnage class. While the "Performance Cooling Data" is listed at a 95-F outside ambient temperature, you can adjust the indoor airflow to get the Nominal BTUH Rating at the customer's normal indoor stat' temp' setting and the most outside temperature/degree operating hours. Take the "listed watts" of the compressor and Condenser fan and multiply that wattage by 0.85 X's 3.413 to get the BTUH heat additive of the motor then add the listed BTUH of the condenser to it, and then divide by the condenser fan's CFM. By using the various units' "base specification sheet data" from the dealer, you can determine if it is operating near its BTUH capacity rating. Some packaged units run a very high condenser discharge CFM airflow! Some "Condenser Makes" will have different temp-splits. The 2-ton 10-SEER, Janitrol; GMC; Goodman; with the U-29 E-Coil delivers less btuh, or 23000-btuh, I subtracted a reasonable amount from the total of the wattage and come up with 19 to 20-F temp-split. That is "if" its CFM is 1400, --get the figures on the "different Makes." The figures are used to provide an idea of what the condenser temp-split should be for use by the unit's owner and the service tech. With a properly sized system and proper evaporator airflow you will have consistent optimal nominal capacity heat absorption and removal coupled with the requisite longer run-time cycles. I believe that optimal efficiencies, with variable latent/sensible heat loads, could be effectively achieved through the use of computerized control system components. For efficiencies sake,
do this immediately. Measure the "Return
Air" duct/chase area. If it's a
round duct measure the inside diameter, I'll give you the sq.ins. For "Return Air" Sizing: Take your air conditioner's btuh and divide it by 120, (or dividing 24,000-btuh by 150 will give you 160 sq.ins., close to a 0.10" return air duct Static Pressure drop) to get the amount of free air square inches for the Return Air duct system. A 4-ton condensing unit, 48,000 btuh would need 400 sq.ins. or two 16" rd. ducts. A 5 ton 60,000 btuh calls for 500 sq. ins., or two 18" rd ducts for 510 sq.ins. A two ton 24,000 btuh takes 200 sq. ins., or one 16" rd. duct. For a 18000-btuh or 180 sq. ins., go with the 200 sq.in. 16" rd. duct. This will permit building more pressure at the supply air diffuser grilles providing more throw across the room. Before you make all the recheck tests, it is very important that your condenser coil and evaporator coil and indoor blower wheel be truly clean. This AC system would have to be sized to the combined latent and sensible heat load targets (i.e., 75F/50RH) and the cubic foot volume of air changes that we would like per hour. This would need to be performed accurately to achieve the requisite run time, and CFM airflow through the cooling coil, to achieve our combined comfort zone and unit efficiency goals. Proper
duct sizing and location
is important. If you have a high ceiling supply air and return air
ducts
should be at the floor level so you can take advantage of air
stratification.
There is no need to cool the air above the occupant height level. I'm talking about any heatload that might be excessive at 475-cfm per ton of cooling. The combination of being real hot outdoors & hot indoors can lead to an overloaded condenser. Also, in some cases we are using a larger tonnage cooling coil. Most older homes need reduced ambient air infiltration and more effective use of vapor barriers coupled with adequate insulation. Windows are special areas to work on. My upstairs windows around the pulley wheels allowed air to blow in unrestricted from the attic area winter and summer.All air conditioning condenser manufacturers' should publish the CFM and normal temperature rise range across the condenser coil, so that the service tech's can measure the heat transferred from the evaporator coil. Most high efficiency units will have temperature degree rises between 18 and 25ºF. Older lower SEER condensers can have temperature rises up to 30 degrees. Such temperature rise data provides a guide to the actual heat transfer by the evaporator coil to the outdoor condenser coil, and therefore also, whether the proper design amount of (cubic feet per minute) CFM of indoor air/per ton of cooling BTU/HR, is passing through the heat absorbing cooling coil. Let's say
you had 0.20-IWC without evaporator coil," then due to the large oil
furnace heat exchanger near the bottom of the E-Coil you add the 0.20
IWC, the coil adds 0.20 IWC for a
total of 0.70IWC. That is without adding everything else!
Additionally, the pressure & velocity drop is where you do not want
it. You want all of the pressure & velocity possible at the
diffusers to get the requisite CFM & throw!
Check the static pressure with a wet coil then check the Units Blower Curve Chart to see if you are getting 375 to 450 CFM per ton of cooling, depending on the humidity removal needs. Is your motor horsepower, blower wheel size and blower RPM up to the task? Subtract 50 cfm from the cfm derived from the formula for the wet cooling coil cfm. It may not be getting the requisite 375 to 450 cfm per ton of cooling, especially if there is a low demand for heating in your area and a high demand for cooling tonnage, or the cooling coil is too close to the oil furnace's heat exchanger causing a restriction and a lot of turbulence back pressure, running static pressures as high as 0.75 or higher water column static pressures (view blower curve chart). Owner's of AC systems should check the return air filters frequently and the blower wheel squirrel cage curved blades for dust and lint accumulation. If the blower wheel and motor are dirty the evaporator fins and coils will need to be checked on the air entry side, all components must be cleaned to regain btu/hr heat transfer efficiency to original specifications. It will cost you big-time on your cooling costs if you don't keep the blower wheel blades and the cooling coil clean. Also, the blower motor is air cooled and will overheat and burn out prematurely. The condenser coils and fins must also be clean. Never use household detergents, most detergents have an oil base that will insulate coils and fins which will reduce the evaporator & condenser coil's heat absorbing efficiencies. Use only the proper AC coil cleaning fluids for for cleaning the indoor and outdoor air conditioning heat transfer coils. High pressure water can be used but you must never bend the coil's heat transfer fins, so keep the stream perfectly straight with the fins. Typically, a system is designed where the appropriate fixed sized metering device bridges (or matches) condenser capacity to evaporator capacity as dictated by the compressor and a specified CFM at a specific temperature/humidity heatload point. With a TEV refrigerant control to the evaporator coils, the CFM range can be any workable CFM from 350 to 450 CFM per ton of condenser cooling capacity. Variable speed blower fan motors "that will provide those 350 to 450 CFM/ton, would be ideal," or adjustable speed belt drive blowers allow the technician to provide the evaporator coil with an optimal heat load at normal indoor temperature and humidity levels. If these factors are ignored and are out of the required specifications your new unit won't deliver the btu/hr or the SEER you paid for. Your new 12 or 14 SEER may be delivering only 8 or 9 SEER. Subject:
What design for lower duct
static and lower blower motor HP? Need for Low
Flow Resistance Residential Duct Systems For instance a duct system moving 800 cfm with a pressure drop similar to that measured in a study (0.63 IWC without coil and 0.83 with the evaporator coil) would result in a power draw of 347-Watts. However, a duct system with a total pressure drop of only 0.20 IWC, or 0.40 IWC with the evaporator coil would produce a power demand of only 167 Watts -- a fan power reduction of 52%. If the compressor electrical demand was 1800 W to produce 24,000 Btu/hr (7032 Watts) of cooling at the coil (not including fan energy), the improvement would alter EER from 10.63 to 11.91 Btu/W -- a 10% net increase in cooling efficiency and capacity. One HP = 746 watts: with S.P. @0.83" | 347 watts / 746 = 0.465 HP or a Half HP Motor | with S.P. @0.4 | 167 watts / 746 = 0.2238 or 0.25, or a quarter HP motor. Properly sized and laid out ducting is critically important to performance. The larger AC units are usually short changed on return air filtering area! Figure the sq. in. of your furnace's return air filter. Furnace free area return air filter area should be sized for the largest AC unit it will handle! The heat-load is determined by the amount of heat the evaporator coil is absorbing from the conditioned areas' --air flowing through it at an optimal CFM heat-load level will properly load the compressor and condenser. Let's take a closer look at the effects of a low heat load on an evaporator coil with a evaporator temperature controlling TEV refrigerant control. The lower heat-load will cause the temperature sensor bulb to reduce the flow of liquid refrigerant into the evaporator coils resulting in a lower than normal suction pressure which reduces the volumetric capacity of the compressor, and liquid refrigerant will begin to back up in the condenser coils which also reduces its capacity. This means that your entire cooling system, (which includes the ductwork design), would NOT be delivering the unit's rated BTUH. Lack of an adequate airflow heatload through the evaporator coil will reduce the BTUH transfer of heat by the evaporator, therefore to the compressor and condenser and on to the outside air. Under very light heat-load conditions the subcooling might appear close to Normal. However, the BTU capacity of the system would be lowered as would the SEER rating because the total amp draw of the system does not drop enough from a fully heat loaded BTU design capacity to come close to the resultant inefficiency. A fixed orifice would begin to flood the evaporator with liquid refrigerant reducing its capacity, because there wouldn't be a sufficient heat-load to vaporize it. Liquid refrigerant could flood back to the compressor causing irreparable damage. The relationship between head pressure variation with liquid subcooling and suction superheat is not the same with TEV/TXV when compared to fixed orifice. With a fixed orifice, the relationship is immediately obvious to experienced tech's. When condenser dT (temperature difference) is very low, a static pressure fan-curve-graphic chart check-up, is required procedure. "On older retro-systems" ("break out your Magnehelic / manometers") this procedure is essential "before attempting to charge a TEV system or fixed orifice on older systems" --that may have serious airflow heat-load mismatches. Additionally, a liquid line sight glass near the evaporator coil is a help, in that you can recover refrigerant until it begins to bubble. Then add charge according to the manufacturer's Return Air ºF match to the wet bulb / dry bulb listed Temp. difference figures, —Superheat charging table, while also monitoring liquid line Subcooling. Service
techs' put your Magnehelic gauge and Digital
Micromanometer to good use to measure
the static
pressure and then get and apply the blower curve charts on each system
you are working on, then you know you're getting the proper evaporator
airflow temperature and heat-load to meet the customer's desired
humidity
and temperature comfort zone. It is always very good practice
to measure the external static pressure on all
systems; you
can do
this with a simple magnehelic gauge or with a digital micromanometer.
In
any case, static pressures above 0.45 IWC should be investigated and
reduced
if at all possible.
Service techs' use your sling-psychrometers' and do the job right. With
an
Insufficient
Heat Load on
the Evaporator COIL: Air
Infiltration sources DTI
Corp Catalog Insulation
& Weatherization Costs Forum
Knowing
the operating static pressure is a first order essential to revealing
the
operating CFM. If ductwork retrofitting doesn't solve the problem;
Blower
wheel RPM and blower motor Horse Power may need to be increased to
achieve
the optimal CFM to achieve your Unit's rated nominal BTUH and Energy
Efficiency
Rating. (80% don't !) There
ought to be a code requiring every manufacturer of an airhandler or
furnace
to provide capped taps ahead of the evaporator coil and ahead of the
blower
for easy static pressure testing access.
Read the pressure on the gauge, and record the reading on the supply side, then on the return side. Use a (+) sign before the positive or supply side reading to show where it was taken, and a (-) sign before the negative or return side reading. Add the two pressures. Disregard the positive and negative signs before the pressures, because both negative and positive pressures affect the fan as a force, so they must be added together to determine the total resistance the fan has to overcome. For example a +.35" I.W.C. plus a -.25" I.W.C. equals a total static pressure reading of .60" I.W.C. Record the pressure
readings on a diagnostic report or on your service ticket. Write the
pressures
on the cooling coil for future reference and use. Any future changes in
static pressure reveals a change in the system that should be addressed.
Finding the New Static Pressure: |
SP2 = (rpm2/rpm 1)2 X SP1 = SP2
Required fan motor horsepower (hp) varies as to the cube of the rpm speed:
hp2 = (rpm2/rpm1)3 x hp1 = hp2
CFM Fan delivery varies directly as to the fan RPM speed:cfm2 = (rpm2/rpm1) X cfm1 = cfm2 A few calculations and presto, a matched airflow with your systems' heat absorbing coil capacities, delivering near its BTUH, EER, and SEER ratings at normal room temperature settings! (Most don't)You will need a good service tech to make the proper tests, and perform the proper adjustments. Utilizing numerous other energy savings techniques, you'll save tons!
Below, PDF File: ThermoPride Blower-Curve-Chart - Click Print , Click on Properties, Click on Graphics, Slide Setting to the Darkest Setting, click OK, or blower curve lines won't show up on the printed copy! (for Techs)
My scan of my doctored Thermopride OL 11
http://www.udarrell.com/Blower_Curve_Graph.tif
SL11B.pdf PDF File: Blower curve lines show in (blasted) yellow, use darkest printing page settings to get readable lines! Every manufacturer should furnish blower curve charts with their units and put them on the Internet for service tech's to download and print. Also, air conditioning codes should be updated in respect to proper sizing of the duct work which must include all the pressure inducing factors when sizing the supply and return ducts.
TEL ASP FR Chart Graph Loads slow using dailup - Save both the pdf to a quick access PC folder for review
Designing or Redesigning Duct Systems Chart PrintDISCLAIMER:
Federal Refrigerant Licensed - Retired Licensed Tech & Contractor
I assume NO responsibility for the USE of any information I post on any of my Web pages, in E-Mails or News Groups.
All HVAC/R work should always be done by a licensed Contractor & properly licensed Techs!
This information is only placed on these pages primarily for your understanding & communication with contractors & techs.
This information is also for the edification of Contractors and Techs. Never attempt anything that you are NOT competent to do in a SAFE manner!
I am NOT liable for your screw-ups, you are liable for what you do! - Darrell Udelhoven
Please write me if you have anything you'd like to contribute! - Darrell Click here to tell a friend about this Web sitePlease feel free to link your web pages to any of mine
- ac-trouble-shooting-chart.html I'm finally posting this page I created long ago
- AC Superheat and Subcooling
- The Air Side of Air Conditioning - Static Pressure
AIR-CONDITIONER RUNNING TOO MUCH
3.5-ton system getting less than 1.5-ton of capacity! Low charge - plus
Link below, 3.5-ton to less than 1.5-ton, too! - Way Overcharged
- Excessive Airflow coupled with an Excessive Charge will greatly reduce AC capacity
Air Conditioning SEER Levels - Are you losing 15 to 50% under SEER & Capacity Rating? style="background-color: rgb(204, 204, 255); font-family: helvetica,arial,sans-serif;">- Determining Your Air Conditioner's Actual BTUH Capacity Output
Proper Sizing of Residential Heating & Air Conditioning Ductwork SystemsAir Conditioning Engineered for Latent Heat Removal For high humidity climates
- An Air Conditioning and Heating Efficiency Check Up - Contractor
- Air Conditioning System Sizing for Optimal Efficiency
- Air Conditioning - Latent Heat Removal Comfort-Zone Efficienc
- FINDING the LATENT HEAT of CONDENSATION of Your Air Conditioner
- Optimizing Room Air Conditioner's EER
- OIL HEATING AIRFLOW TEST Using Thermometers -
- Best Practices Guide for residential HVAC retrofit
- New TEC Energy Conservation Testing TechnologiesNew!
- Energy Star New!
Study the Failure Rate Graph - Great Information! - pdf#1 Residential Forum - HVAC Talk Community
GARDEN WEB - Heating & Air Conditioning Forum - New
DIY Do It Yourself Forum" "Do It Yourself" TV- I Am "HVAC RETIRED"
HVAC Discussions Mike Holmes HVAC Forum - New
Refrigeration Engineer Forums - New
MY HVAC BLOG - YOUR QUESTIONS & COMMENTS WELCOME
Cynergy Home HVAC Energy Raters Listen While Reading
- EMPOWERMENT COMMUNICATIONS
*Video checking static ESP| *Video 2 checking static ESP View! I Got DSL 11/2010
Air Flow CFM of a very large Supply Air Register using a Testo 410 Vane Anemometer Basic...
*Video measuring airflow Velocity W/ anemometer on a Return Air grille
He programmed it in, because when I did the math using .90% for the grille I got 336.57863-FPM Vel *X 2.376562-SF free-air-area= 799.9-CFM, or 2-Ton of airflow.
I'd use close to .50% for the free-area of a clean FILTER, & .90% factor for open grille area.
*Basics Featuring the Testo 556 - Video of a very thorough Air Conditioning Testing setup 2/26/11
Realtime HVAC A/C BTUH Performance Output (Part 1 of 2) YouTube Video
*Realtime HVAC A/C BTUH Performance Output (Part 2 of 2)
-----------------------------------------------------------------------------------------------
Darrell Udelhoven - udarrell
Empowerment Communications
Covering The Real Political Issues
Posted: 05/14/05; Edited: 01/08/13
Darrell, Darrell Bloomington, Lancaster, Grant County, SW WI