| "Higher" or "Lower"
than
"Normal" (PRINT CHART) |
Low-Side |
|
High-Side |
|
|
| NORMAL - (norm) - LOW
- HIGH - Variable |
|
|
|
SUB-Cooling |
|
| (1) Suction Line Restriction - Upstream
Between Service Port & E-Coil |
|
|
|
norm |
|
| (1a)Suction Line
Restriction - Downstream from Service Port At Compressor screen TXV |
Normal
to High |
HIGH |
LOW |
norm |
LOW |
| (2) Restrictive metering orifice; TXV
Starving Coil; Liquid line Restriction |
|
|
|
HIGH |
|
| (3)Evaporator orifice oversized or bypassing - or TXV Overfeeding - Normal
Charge |
HIGH |
usually
- low |
LOW |
norm
- low |
NORMAL-LOW |
| (4) Hot gas Disc. Line Restriction |
|
|
|
|
|
| (5) Inefficient Compressor - Also, see (3) Above |
|
|
|
|
|
| (6) Unbalanced heatload on Evaporator Circuits |
|
|
|
|
|
| (7) Insufficient Evap. Airflow, or
Heatload |
LOW | LOW | LOW | LOW | LOW |
| (8)
Refrigerant Overcharge- High
or Low pressure -Variable
according to
heatload non-TXV |
|
|
|
|
|
| (9) Insufficient Charge - piston
orifice |
LOW | HIGH | LOW | LOW | LOW |
| (9a) Insufficient - Fairly Low
Charge with TXV
Wide Open |
Normal
|
HIGH |
LOW |
LOW |
LOW |
| (10) Excessive
Evaporator Heat Load - Latent &
Sensible - High Latent |
HIGH |
HIGH |
HIGH |
Usually
Low |
HIGH |
| (11)
Very
High Temp Ambient Air Entering Condenser or dirty - Low
condenser
airflow |
HIGH | HIGH | HIGH | norm |
HIGH |
==========================
Air
Conditioning Performance Diagnosis using listed (CT) Condensing
Temperatures
Using Goodman 16-SEER "Expanded Performance Data"
Find the correct (CT) Condensing Temperature with the following
known mfg’ers data.
Outdoor Ambient Temp (OAT) 85-F; IDB 75-F; IWB 63-F or 50%-RH.
Listed pressure is 316-psig, or 99-F CT; that is 99-F -85-F is a 14-F
SPLIT.
The delta T or temp-split should be within a 10-psig range or, +/- 2-F
degrees; 97 or 101-F.
The mfg’ers Supply Outlet should be able to provide Contractors &
Techs with those performance data charts. Goodman has their “Expanded
Performance Data” on the Internet. BTUH = CFM X
enthalpy difference from Chart X 4.5
<-Click
For
efficiencies sake measure the
Return Air duct/chase
area. If
it's a round duct measure the inside diameter, I'll give you the sq.
ins. formula on another pages;
if square or rectangular multiple the two dimensions for sq. in. area.
The sq.in. Return Air throughput ducting area should equal or exceed
the
Supply Area ducting. In the far north smaller A/C units
Verses
the new larger heating blower units can mean too much CFM for the A/C's
smaller BTUH capacity. Thermostatic
Expansion Valves (TEV / TXV) systems should be set for a minimum
10 Degrees
Superheat.
NOTE on 3 & 5 Above: If suction is high & head is low
it is not necessarily an inefficient
compressor, it could be (3) three.
"An oversized orifice or overfeeding TXV
refrigerant metering device" could cause high suction & low head
due
to normal compressor pumping capacity being incapable of keeping up. An
oversized unit might handle the sensible load but never do anything
with the
latent load as the conditioned space temp falls.
"Overcharging" will raise suction pressures & E-Coil temperatures
& though it may raise head pressures, it does not always raise head
pressures. The reason for this is that it reduces the capacity of the
evaporator to absorb both latent & sensible heat & therefore
reduces
the actual heatload on what may possibly be an oversized over-capacity
condenser coil.
Of course, an inefficient compressor could cause this problem; however,
I would
always do the Superheat & Subcooling checks & look for an overfeeding metering device as well as an overcharged system, along with other
possible causes, before ever condemning a compressor.
(8) NOTE:
Refrigerant
Overcharge: amp draw is HIGH when under a
heavy heatload and can be LOW when overcharged but under a light heatload;
both the condenser and evaporator are then overloaded with liquid and
there
is not enough of a heatload to evaporate sufficient amounts of
refrigerant in the E-Coil to INCREASE PRESSURES and pumping WORK.
After any duct work or other changes and before you make any recheck tests, it is very important that your condenser coil, evaporator coil, and indoor blower wheel be squeaky clean.
Take the condenser entering air temp and leaving air temp, subtract for the temp-split. As a double verification: You can use the manifold gauge high-side (SCT) Saturated Condensing Temperature-dial-reading minus the outdoor-ambient temperature; the difference gives you the condenser temperature/split. There is NO excuse for not utilizing this simple btu/hr operating capacity diagnostic check. Always use an accurate volt meter and amprobe to make sure you are not overloading the compressor's amperage Service Factor and check the compressor discharge line to see that it is under 225-F.
=======================
Quick
Check for Sizing Units to enough Airflow
Actually, even on service calls where there are cooling
problems the ductwork should have a quick Manual D performed.
Then take the
ESP
static pressure & compare to blower graph or chart, also take the
FPM duct velocity.
Then do a quick
estimate of airflow
per equipment tonnage.
To find area of
a
round duct; Duct diam is 7"; 7"X7"= 49-sq.ins., X's .7854 =
38.04845-sq.ins divided/ by 144= 0.2672541-sq.ft. area X's FPM Velocity
600-FPM = 160.35246-CFM X30 = 4,810.5738
each 7" run X's 6 branch runs
= 28,863-BTUH, or airflow for 2.4-ton.
(12,000-BTUH
/400-cfm per-ton = 30-BTU per cfm ratio | / 450 = 26.666-BTUH per-cfm)
That would also
be
good for 2-ton; at 550-FPM velocity X's 0.2672541= 147-CFM X 30 =
4,410-BTUH each run X 6-runs = airflow for 26,460-BTUH.
*Never sell
units requiring more airflow than the duct system will support! - Darrell
======================
Target
Temperature Split for Airflow Chart
Print the linked pdf TEMP-SPLITS chart only, ignore the
super heat
chart.
Upper right corner, blank out RA WB Temps above RA DB Temps, PC kept
figuring the errant ratio.
First,
thoroughly seal
all
ductwork with an approved mastic!
INTRODUCTION TO
TOTAL COOLING PERFORMANCE;
How installing a 3-ton system can become a 1.5-ton system of actual
delivered cooling (SURPRISE!):
http://epb1.lbl.gov/residential/cool.html
To get
the
gross BTUH
Heatload the Evaporator (DX) Coil is absorbing (which includes both
latent,
sensible heat) (These are ARI
Formulas)
First, determine
the
Gross Rated BTUH the condenser is ejecting.
Condenser’s Gross
Btuh
= Condenser’s rated CFM X’s
Temp Split X’s
1.08
CONDENSER
TEMP-SPLITS
- My Brother's Heil 12-SEER Condensing Unit
1.5-Ton - Rated
at
17,500-BTUH, Condenser fan CFM 1400 (Total Cond. Watts 1591 X's
power Factors0.90
X's= 1432 X's * 3.413 = 4887-BTUH Motor Heat additive
+17,500= MotorPower
"Rated Gross Heat Ejection" is 22,387-BTUH / 1400= 15.99-F x 1.08= 17.27
Temp Rise Cond/Split. His condenser only gets a 10 to 12 temp
rise
split, the evaporator appears to be under heat-loaded or, an unbalanced
heatload on the DX coil's circuitry.
The
probable
cause is
"an unbalanced airflow
heatload
through the evaporator coil. "It's a (Thermo Pride OL 11 oil
furnace).
Those oil furnaces have a very large round heat exchanger that goes to
near the top of the furnace, --due to a low basement ceiling the DX
coil
sets perhaps illegally close to the heat exchanger causing a few of the
coil's circuits to be under heatloaded. Since the liquid refrigerant is
not completely evaporated it will cause the outlet line that the TEV
sensor
bulb is on to be too cold and the TEV will shut-down the flow, which
greatly reduces the BTUH capacity of the DX coil and the system.
So, your unit is costing you a fortune, I need to have the
temperatures below, - that you can easily take for me:
“Copy only the data portions & paste in your
Word-Processor, make a couple hard-copies, then send me what you take,
& get as much of this data as your Tech will provide for you.” You
can delete the (You &/or Tech) before you make hard copies for your
Tech. Techs & HVAC user's, please use to your heart's content.
This is very important: Always tell the tech that you want all the data he takes clearly recorded on the Service Receipt!
I can run the temperatures data you take with an accurate CFM Airflow & ball-park the Nominal BTUH your new A/C is delivering, at those conditions.
TROUBLE SHOOTING DATA - (You or Your) HVAC Tech
For my information concerning summer design & your climate,
provide your state & nearest large city __________
TONNAGE of Unit or outdoor condenser model number:
___________ You
TXV or orifice metering device? _______You or Tech, - not real critical
to this analysis
Outdoor condenser’s discharge-air-temperature _____You
Out-Door temperature: ____You
Condenser air Temp split _____You
Indoor Total-ESP
- External Static Pressure _______Tech
All Supply Air velocities in FPM: ___Tech
I’ll do the
math for the total CFM:
Suction line pressure ___Tech
Suction-Vapor line temperature: ___Tech
Saturated Suction Temp – Gage - Suction Saturated Temperature. ___Tech
Superheat
______Tech
Head pressure _______Tech
SCT – Gage - Saturated Condensing Temp _______Tech
Small Liquid line - temperature: _______You
Subcooling:
_______
Return Air temp DB &, WB or %RH: _______You
Supply Air temp DB &, WB or %RH: _______You
With the information data below and an accurate Cubic Feet per
Minute (CFM) airflow, I can
ball-park
the Units BTUH output
Return Air temp DB &, WB or %RH:
____ ____You
Supply Air temp DB &, WB or %RH:
____ ____You
Take a cotton cloth & wet with
room temperature water, wrap it
around the thermometer & use it for the wet bulb temps above.
Except for the Pressures, Superheat & subcooling you can take most of the other Temp readings for me.
My advice: to every user, get a low cost humidity gage at a local hardware store & see what the percentage-RH is in your home, I can cross-reference that to the wet bulb depression so you could use the humidity gage instead of wet or use both.
If you want to save money you will take the time when it is hot & warm in the house to take all this temperature data!
Please Respond, ASAP.
Anyone is welcome to use the Data Collection for use as they see fit!
“Copy only the data portions & paste in your Word-Processor, make a couple hard-copies, then send me what you take, & get as much of this data as your Tech will provide for you.”
My monthly electric bills run $50.00 or less, & I keep very cool, in a 1937 farm home, even in 104-F Heat Index!
Are your electric bills too high?
udarrell - Darrell, Retired HVAC from mid 1970’s
=======================Too many do not properly purge & evacuate contaminated central air conditioning systems.
The Triple Evacuation Method is normally done on refrigeration systems, R-410a systems require it on central air conditioning systems:=================================================================
The condenser
fan speeds
are slower on several of the 10-SEER Tonnage Models.
We are only
trying
to get a figure to go by for a comparison. When new condensers and
Evaporator
coils "are installed on older air handlers" the new, or old,
evaporator
coils are usually under heat-loaded. (Always, check voltage and
amp draw!)
The Base Spec
sheets
12-SEER part no. 421 41 33301 03, Feb 2001. These are the
Comfortmaker®
units, which are nearly identical to Heil® units. I used the first
rating on each tonnage class. While the "Performance Cooling Data" is
listed
at a 95-F outside ambient temperature, you can adjust the indoor
airflow
to get the Nominal BTUH Rating at the customer's normal indoor stat'
temp'
setting and the most outside temperature/degree operating hours.
http://www.udarrell.com/air_temperature_drop_evaporator.jpg
Below
is an outstanding PDF "Basic AC Overview - Specifications VS. Reality"
by John Proctor, P.E., Proctor Engineering Group, LTD:
DISCLAIMER:
Any
of
the HVAC companies I list on any of my web pages have nothing to do
with the information I post on any of my Web pages nor do I garantee
its accuracy or assume any
responsibility for how anyone uses that information.
All HVAC/R work
should always be done by a licensed Contractor! This information is
only placed on these pages for your understanding & communication
with contractors & techs.
This
information is for the edification of contractors and techs. I
am NOT liable for your screw-ups, you are liable for what you do! -
Darrell Udelhoven
#1 HVAC Talk Community
MY GLOBAL ECONOMIC Policy PEOPLE EMPOWERMENT PAGES
Darrell Udelhoven