| "Higher" or "Lower"
than
"Normal" (PRINT CHART) |
Low-Side |
|
High-Side |
|
|
| NORMAL - (norm) - LOW
- HIGH - Variable |
|
|
|
SUB-Cooling |
|
| (1) Suction Line Restriction - Upstream
Between Service Port & E-Coil |
|
|
|
norm |
|
| (1a)Suction Line
Restriction - Downstream from Service Port At Compressor screen TXV |
Normal
to High |
HIGH |
LOW |
norm |
LOW |
| (2) Restrictive metering orifice; TXV
Starving Coil; liquid line Restriction |
|
|
|
norm |
|
| (3)Evaporator orifice oversized or bypassing - or TXV Overfeeding - Normal
Charge |
HIGH |
usually
- low |
LOW |
norm
- low |
NORMAL-LOW |
| (4) Hot gas Disc. Line Restriction |
|
|
|
|
|
| (5) Inefficient Compressor - Also, see (3) Above |
|
|
|
|
|
| (6) Unbalanced heatload on Evaporator Circuits |
|
|
|
|
|
| (7) Insufficient Evap. Airflow, or
Heatload |
LOW | LOW | LOW | LOW | LOW |
| (8)
Refrigerant Overcharge- High
or Low pressure -Variable
according to
heatload non-TXV |
|
|
|
|
|
| (9) Insufficient Charge - piston
orifice |
LOW | HIGH | LOW | LOW | LOW |
| (9a) Insufficient - Fairly Low
Charge with TXV
Wide Open |
Normal
|
HIGH |
LOW |
LOW |
LOW |
| (10) Excessive
Evaporator Heat Load - Latent &
Sensible - High Latent |
HIGH |
HIGH |
HIGH |
Usually
Low |
HIGH |
| (11)
Very
High Temp Ambient Air Entering Condenser or dirty - Low
condenser
airflow |
HIGH | HIGH | HIGH | norm |
HIGH |
|
First, always check for Return Air/Supply
Air duct leaks, seal them with approved mastic, check CFM airflow rate
and that the coil fins and blower wheel blades are clean! "Check for
Insufficient Air Flow Across Evaporator Coil" - Check for: dirty
filter, dirty lint clogged evaporator, blower speed tap selected, or
belt and speed adjustments, blower motor, check any belts for
wear and proper tension, dirt lint loaded blower wheel, and out of
specs or wrong rated run capacitor.
Check airflow system static pressure. Verify Blower Performance --by checking blower air handler "Static Pressures with the specific model's Blower Curve Charts." At a specific heatload condition, Optimize the conditioned space's heatload on the evaporator coil to optimize the rated Btu/hr and EER, and/or SEER Ratings. First, Check Return Air (RA) at grille & at entry of blower for heat gain, due to Return hot Air leaks. Where air handlers' are set over Return Air Chambers, check for air leaks through the sheet rock & down the wall studs from the attic - this is a fairly common condition that will overload the AC system with attic heat! Airflow has to be optimal & within specs before the refrigerant charge can be correctly charged! Check Return Air (RA) at grille & at entry of blower for heat gain, due to hot Return Air leaks. Where airhandlers' set over Return Air Chambers check for air leaks through the sheet rock & down the wall studs from the attic - this is a fairly common condition that will overload the AC system! For
efficiencies sake measure the
Return Air duct/chase
area. If
it's a round duct measure the inside diameter, I'll give you the sq.
ins. formula on another pages;
if square or rectangular multiple the two dimensions for sq. in. area.
The sq.in. Return Air throughput ducting area should equal or exceed
the
Supply Area ducting. In the far north smaller A/C units
Verses
the new larger heating blower units can mean too much CFM for the A/C's
smaller BTUH capacity. Thermostatic
Expansion Valves (TEV / TXV) systems should be set for a minimum
10 Degrees
Superheat. NOTE on 3 & 5 Above: If suction is high & head is low
it is not necessarily an inefficient
compressor, it could be (3) three. (8) NOTE:
Refrigerant
Overcharge: amp draw is HIGH when under a
heavy heatload and can be LOW when overcharged but under a light heatload;
both the condenser and evaporator are then overloaded with liquid and
there
is not enough of a heatload to evaporate sufficient amounts of
refrigerant in the E-Coil to INCREASE PRESSURES and pumping WORK. After any duct work or other changes and before you make any recheck tests, it is very important that your condenser coil, evaporator coil, and indoor blower wheel be squeaky clean. Take
the condenser entering air temp and leaving air temp, subtract for the
temp-split. As a double verification: You can use the manifold
gauge
high-side (SCT) Saturated Condensing Temperature-dial-reading
minus
the outdoor-ambient temperature; the difference gives you the condenser
temperature/split. There is NO excuse for not utilizing this simple
btu/hr operating capacity diagnostic check. Always
use an accurate volt meter and amprobe to make sure you are not
overloading
the compressor's amperage Service Factor and check the
compressor
discharge line to see that it is under 225-F. Target
Temperature Split for Airflow Chart First,
thoroughly seal
all
ductwork with an approved mastic! To get
the
gross BTUH
Heatload the Evaporator (DX) Coil is absorbing (which includes both
latent,
sensible heat) (These are ARI
Formulas) The
chart split listed below is at Condenser Design conditions: Indoor
Return
Air 80-F dry bulb 67-F Wet Bulb or 50% Relative Humidity as you go up
to
99% RH the condenser split could increase by up to 6-F; down as much as
4-F at a low humidity of 55-F Wet Bulb.
CONDENSER
TEMP-SPLITS - Comfortmaker® 12-SEER units - used 0.90 Motor Power
Factor The chart split listed below is at Condenser Design conditions: Indoor Return Air 80-F dry bulb 67-F Wet Bulb or 50% Relative Humidity as you go up to 99% RH the condenser split could increase by up to 6-F; down as much as 4-F at a low humidity of 55-F Wet Bulb. Do your own figuring based on this formula. Motor BTU/hr additive = Watts X's PF x's 3.413 for Btu/Watts additive added to rated BTUH, divided by condenser fan CFM X's 1.08 = condenser Temp-Split. Get the Motor "Power Factors" (PF) of the compressor and fan motor from the manufacturers. Some Splits rounded. 1.5 T 17,500 -17 Split Cond. CFM 1400 WATTS 1591x.90=1432x3.413=4,887+17500=22,389/1400=15.9x1.08=17.3 2-Ton 24,000 23-F Temp-S Cond. CFM 1400 WATTS 2067x.90=1860x3.413=6349+24000=30349/1400=21.7x1.08=23.4 2.5-T 30,000 21-F Temp-S Cond. CFM 2000 WATTS 2778x.90= 2500=8533+30000=38533/19.2x1.08=20.8 3-Ton 35,600 14.8-F T-Sp Cond. CFM 2800 WATTS 3096x.90= 2786+35600=38386/2800=13.7x1.08=14.8 3.5 T 42,500 17.6-F T-Sp Cond. CFM 2800 WATTS 3578x.90=3220+42500=45720/2800=16.3x1.08=17.6 4-Ton 48,500 19.5-F Split Cond. CFM 3400 WATTS 4174x.90=3756.6x3.413=12821+48500=61321/3400=18x1.08=19.5 5-Ton 59,000 23-F Temp-S Cond. CFM 3400 WATTS 5043x.90=4539x3.413=15,490+59000=74490/3400=21.9 CONDENSER
TEMP-SPLITS
- My Brother's Heil 12-SEER Condensing Unit The
probable
cause is
"an unbalanced airflow
heatload
through the evaporator coil. "It's a (Thermo Pride OL 11 oil
furnace).
Those oil furnaces have a very large round heat exchanger that goes to
near the top of the furnace, --due to a low basement ceiling the DX
coil
sets perhaps illegally close to the heat exchanger causing a few of the
coil's circuits to be under heatloaded. Since the liquid refrigerant is
not completely evaporated it will cause the outlet line that the TEV
sensor
bulb is on to be too cold and the TEV will shut-down the flow, which
greatly reduces the BTUH capacity of the DX coil and the system.
On
piston
refrigerant
control systems, they may flood
back liquid which
could damage the compressor, unless the system is way under-charged.
Thermo
Pride could install airflow turning vanes just above the heat exchanger
to funnel the air directly into the DX coil, instead of most of the
airflow
hitting the bottom of the DX's drain
pan causing extreme turbulence
back-pressure and an imbalanced circuitry DX coil heatload!
His unit could also have some low temperature solder trapped on the screened entrance to the TEV evaporator metering device. If there is a gurgling noise& temp drop there, any restriction there would also lower the capacity of the cooling coil. ===================== Gurgling Pulsating Sounds at TXV: Low evaporator heat-loads lead to reduced liquid line mass and increased evaporator mass could be due to airflow problems. Eliminate low evaporator heat-loads before looking into adjusting the refrigerant charge. Gurgling and pulsation noises at the expansion device can be caused by low evaporator circuit heat-loads, low charge, and/or non-condensibles and moisture in the system. Unbalanced airflow through the various distributor circuits of the evaporator coil will cause the TEV to close down refrigerant flow starving the coil. Piston-flow-rators will make it impossible to properly charge the system and cooling will be greatly compromised unless you eliminate the cause! "Put your ear on the liquid line at the evaporator coil." On every Rheem condenser cover it lists "non-condensibles and or moisture" as causes for a gurgling or pulsating noise at the expansion device. The entire evaporator circuits, may not become active for various reasons, - "the entire coil must become fully active for efficient performance." The purpose of these recommendations is to provide liquid refrigerant at the expansion device and provide efficient operation. Hopefully, this will aid your research. If I can be of additional assistance, contact me. ----------------------------------------------------------- Too many do not properly purge & evacuate contaminated central air conditioning systems. The Triple Evacuation Method is normally done on refrigeration systems, R-410a systems require it on central air conditioning systems:First, remove any valve cores with a special valve core remover this will speed up the evacuation time. Back service valves two turns off their back seat. 1) Re-claim unit charge (Recover all the refrigerant) 2) Charge system to 150 PSIG with dry nitrogen and leak test 3) On contaminated systems replace the filter dryers. Then Repair all leak(s) 4) Evacuate system to 500 microns valve off & see if it holds 500 microns for ten minutes, if it holds, break the vacuum with dry nitrogen 5) Evacuate system to a deeper 400 microns, valve off vac pump, & again break the vacuum with dry nitrogen 6) Evacuate system to 400 microns and & then Check to see if it holds. (Recharge with fresh clean refrigerant) 7) Check to see if the Supply and Return air ducts were correctly sized & sealed by the original installer. If a vacuum pump will not evacuate a system below 1500 microns there is a problem with the pump itself, a leak in the system, or moisture in the system. Moisture is most likely because water vaporizes at 1500 microns. Many HVAC contractors will consider this excessive time & effort for contaminated residential air conditioning systems, however it is a must for low temp applications. The “micron” is a metric unit of measure for distance. The micron is a unit of linear measure; one micron equals 1/25,400ths of an inch. Modern high capacity vacuum pumps help speed up the evacuation process. When a system has been evacuated below 500 microns, the pump is valved-off with the micron gauge connected, if the vacuum rises to 1500 microns and stops, there is moisture remaining in the system. If it rises above 1500 microns & continues to rise there is a leak. You should allow at least 15 minutes after the pump has been shut off an accurate micron gauge reading. When a system will not evacuate below 1500 microns there is either a lot of water or there is a system leak. ================================================================= http://www.udarrell.com/air_return_latent_condenser_split.jpg Click this Important Graph Page 618, Refrigeration & Air-Conditioning (ARI) Second Edition, C 1987 Those lower SEER units had higher condenser splits than 12-SEER and higher units. Sorry, I defiled the graph, 90-db outdoor, 80-db indoors with 67 wet bulb/50% RH represents the condenser splits shown above. The condenser
fan speeds
are slower on several of the 10-SEER Tonnage Models. The Base Spec
sheets
12-SEER part no. 421 41 33301 03, Feb 2001. These are the
Comfortmaker®
units, which are nearly identical to Heil® units. I used the first
rating on each tonnage class. While the "Performance Cooling Data" is
listed
at a 95-F outside ambient temperature, you can adjust the indoor
airflow
to get the Nominal BTUH Rating at the customer's normal indoor stat'
temp'
setting and the most outside temperature/degree operating hours. http://www.udarrell.com/air_temperature_drop_evaporator.jpg Click this Important Graph & Compare to the Condenser Graph As the latent load goes up the indoor split goes down while the condenser split goes up. Air Temperature Drop Through Evaporator Coil (1987 Period) Indoor temperature and humidity load variations graph. Refrigeration & Air-Conditioning (ARI) Second Edition, Page 624, © 1987 Below
is an outstanding PDF "Basic AC Overview - Specifications VS. Reality" DISCLAIMER: This
information is for the edification of contractors and techs. I
am NOT liable for your screw-ups, you are liable for what you do! -
Darrell Udelhoven --------------------------
AIR-CONDITIONER
RUNNING TOO MUCH
|